Alarm
Alarm Name
ID
2036
Grid
Overfrequency
2037
Grid
Underfrequenc
y
Issue 04 (2023-02-17)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
Power grid exception: The
actual power grid
frequency is higher than
the standard requirement
for the local power grid.
Major
Cause ID = 1
Power grid exception: The
actual power grid
frequency is lower than the
standard requirement for
the local power grid.
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Troubleshooting
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The inverter
automatically recovers
after detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check
whether the power grid
frequency is within the
allowed range. If no,
contact the local power
operator. If yes, modify
the grid overfrequency
protection threshold
through the mobile app,
or NMS with the
consent of the local
power operator.
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The inverter
automatically recovers
after detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check
whether the power grid
frequency is within the
allowed range. If no,
contact the local power
operator. If yes, modify
the grid underfrequency
protection threshold
through the mobile app,
or NMS with the
consent of the local
power operator.