LEYBOLD SCREWLINE SP 630 F Operating Instructions Manual

LEYBOLD SCREWLINE SP 630 F Operating Instructions Manual

Dry compressing screw vacuum pump
Hide thumbs Also See for SCREWLINE SP 630 F:
Table of Contents

Advertisement

SCREWLINE
SP 630, SP 630 F
Dry Compressing Screw Vacuum Pump
Operating Instructions GA02411_002_C0
P/N
117 007, 117 008
117 105 - 117 108
117 017 - 117 019 ATEX 3i
117 113, 117 114
117 115, 117 116 ATEX 3i

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SCREWLINE SP 630 F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LEYBOLD SCREWLINE SP 630 F

  • Page 1 SCREWLINE SP 630, SP 630 F Dry Compressing Screw Vacuum Pump Operating Instructions GA02411_002_C0 117 007, 117 008 117 105 - 117 108 117 017 - 117 019 ATEX 3i 117 113, 117 114 117 115, 117 116 ATEX 3i...
  • Page 2: Table Of Contents

    Conforming Utilisation Connection to the System 3.3.1 Connections at the Intake Side 3.3.2 Connections at the Delivery Side (Exhaust) Electrical Connection 3.4.1 Motor Protection 3.4.2 Star/Delta Start-up Circuit 3.4.3 Soft Start 3.4.4 Mains Connection GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 3 Checking and Cleaning the Gas Ballast Filter Replacing the Throttles in the Purge Gas Device Service at Leybold 5.10 Maintenance Schedule Troubleshooting Waste Disposal EC Declaration of Conformity Index These Operating Instructions are the original instructions. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 4 Operating Instructions and follow the information so as to ensure optimum and safe working right from the start. The Leybold SCREWLINE SP 630 and SP 630 F have been designed for safe and efficient operation when used properly and in accordance with these Operating Instructions.
  • Page 5: Important Safety Information

    Reactive or corrosive gases may cause health problems . When the pump has been used to pump reactive or corrosive gases before, introduce corresponding safety precautions before opening it, e.g. wear gloves, breathing protection or protection clothing GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 6 Connect the pump so that it not will restart automatically after a mains power failure, once the power returns. Overhead load Transport the pump only at the crane eye or with a forklift secured on a suitable palette. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 7: Mechanical Hazards

    The crane eye of the screw pump must never be used to lift any pump combinations (Roots pump + backing pump). GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 8: Electrical Hazards

    Covers marked with this symbol must only be opened by trained electricians after having reliably deenergised (lockout/tagout) the equipment. Observe the manufacturer’s information and the Operating Instructions for the respective frequency converter. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 9: Thermal Hazards

    Pump with installed purge gas unit: When operating the pump with a purge gas valve, secure the purge gas supply so that in the event of a malfunction no overpressure can occur in the system. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 10 For this see Section 5.9 Service at Leybold. When shipping contaminated pumps which require approval by the authorities, note the applicable regulations regarding packaging and shipping. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 11: Ignition Risk

    Leybold is not in a position to perform servicing (repairs) and waste disposal of radioactively contaminated pumps. Both needs to be ensured from the side of the user.
  • Page 12: Risk Of Pump Damage

    For proper connection, a suitable motor protection switch must be used. Set this motor protection switch in agreement with the informa- tion provided on the motor nameplate. Connect the pump to the correct mains voltage and mains frequency. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 13 For this refer to Section 4.3 Shutting Down. Pressures given in bar or mbar are absolute values. If exceptionally a gauge pressure is meant, a “g” is added (bar(g) = bar (gauge) = bar overpressure) GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 14: Sp 630 / Sp 630 F Atex Category 3 (Inside) Vacuum Pump

    G For areas with an atmosphere capable of exploding caused by gases, vapours or mists in the air. D For areas with an atmosphere capable of exploding caused by explosive dusts. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 15 Modifying the supplied pump, voids the CE and ATEX Declaration of Conformity. Related Accessories When using accessory components together with the pump it needs to be ensured that these accessories are suited for operation in explosion hazard areas. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 16: Areas Of Application

    It is important to note that the composition of the gas at the intake on the suction side of the pump and at the exhaust to the atmosphere may possibly differ. This may possibly have an influence on the zone assignments (EG Directive 99/92/EG). GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 17 Mechanical sparks Will not occur during normal operation Electrical sparks Outside of the pump due to motor, accessories Static electricity Will not occur during normal operation Chemical reactions Will not occur during normal operation GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 18: Special Requirements For Safe Usage "X

    The maximum temperatures are attained during constant operation at an inlet pressure below 300 mbar (absolute). The actually attained temperature depends on the inlet pressure. Higher maximum surface temperatures can occur when not filling and oper- ating the pump with the oil LVO 210. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 19 A filter on the intake side must be connected to ground in accordance with the Operating Instructions of the filter. Use only the original spare parts from Leybold. Ground Connection Between the M 8 tapped blind hole on the pump (see figure) and the frame ground/ground rail of the frequency converter, an EMC compliant ground connection (copper strap, for example) must be provided.
  • Page 20 In order to ensure that the defined level of safety is maintained, only accesso- ry parts and wearing parts from Leybold must be used. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 21: Description

    Depending on requirements, the screw pumps may be combined with Roots pumps so as to attain higher pumping speeds at lower pressures. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 22 Fig. 1.2 Compression principle and the direction of pumping action within a screw pump without inner compression with inner compression against with inner compression the face side of the pump along the rotor chamber (SCREWLINE) Fig. 1.3 pV diagrams of screw pumps GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 23 In this way the power requirement of the pump is reduced and less heat needs to be dissipated. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 24 (fig. 1.2) so that the chamber volume is already reduced at low pressures (fig. 1.3c). In this way a power consumption can be attained which is comparable to that of rotary vane pumps. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 25: Technical Data

    Intake flange and exhaust flange EN 1092-2 - PN 6 - DN 100 compatible with EN 1092-2 - PN 10 - DN 100 ISO 1609-1986 (E)-100 (DN 100 ISO-K) ASME B 16.5 NPS 4” Class 150 GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 26: Technical Data For The Water Cooling System

    11.0 for cyclic operation 15.0 R = air cooling (Radiator) E = exhaust (Exhaust) D = environment (Dissipation) W = cooling water (Water cooled) Fig.1.4 Heat dissipation at the SP 630 F GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 27 68 – 75 mm for standard pumps 120 – 135 mm for pumps on castors Marks for safe handling by a forklift > 900 > 900 Clearance for maintenance work Fig. 1.6 Dimensional drawing for the SP 630 GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 28: Technical Data Of The Sp-Guard Monitoring System

    Power rating during operation Power rating when being energised 80 W Type of protection IP 65 acc. to IEC 60259 Cable diameter 6-7 mm Electrical connector with Varistor Bürkert, type 8376 acc. to DIN 43650 Form A GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 29: Technical Data Of The Purge Gas Facility

    For the purpose of shipping the pump, the pump has been affixed to a spe- cial pallet. Retain this pallet in case the pump needs to be returned. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 30: Built-In Accessories

    The gas ballast valve is used for the purpose of avoiding condensation within the pump. Purge gas facility (only for certain pump versions) Purge gas prevents that process gas escapes via the two shaft seals to the environment and protects components and seals against corrosion. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 31 117 114 60 Hz purge gas for shaft seal 117 115 50 Hz Water cooling, with solenoid gas ballast and 117 116 60 Hz purge gas for shaft seal ATEX 3i GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 32: Accessories

    215 226 200 - 230 V AC 215 227 Stability of the pump when using Leybold accessories is ensured. If other accessories are fitted then the user himself will be responsible for maintaining pump stability. 1) Only in connection with installed purge gas facility...
  • Page 33: Wearing Parts And Original Spare Parts

    Maintenance kit level 3, SP 630 for axial bearing change, 2 O-rings, 6 gaskets (Cu), 2 angular ballbearings EK110000794 Replacement throttles for purge gas facility EK110000827 Additional spare parts are available from the Leybold service offices. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 34: Transport And Storing

    During such work note that there is the risk of slipping and toppling. If required, secure the pump. For transporting, the silencer must be disas- sembled as otherwise there is the risk of toppling. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 35: Pumps With Castors

    The pump must only be moved on a level floor! Moving to pump along slop- ing paths or ramps is prohibited! At the installation location unscrew with the adjustable feet so that the pump is maintained horizontally, see fig. 2.2. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 36: Storing The Pump

    For this reason before transporting or storing the pump drain out the water. For this, see Section 4.3 Shutting Down. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 37: Installation

    If during maintenance work the covers are removed, there is the risk of suf- fering burns. Therefore always wear the required protective clothing. With all covers in place there only the remains the risk of suffering burns at the discharge port. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 38: Ambient Conditions

    The pumps have been designed to pump air or inert gases in the pressure range between atmospheric pressure and the ultimate pressure of the pump. If other gases are to be pumped with this pump, please consult Leybold first. For Part Numbers 117 017 - 117 019, 117 115, 117 116...
  • Page 39: Connection To The System

    The materials for the connecting lines must be capable of sustaining the medium which is being pumped. The pipe connections shall be connected to the pump free of any mechanical tensions. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 40: Connections At The Intake Side

    Remove the protection foil and desiccant from the discharge flange. CAUTION The pressure in the discharge line must not exceed 200 mbar are above the ambient pressure. The discharge line must not be blocked or constrict- GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 41: Electrical Connection

    The number of operating hours of the pump is acquired through the SP-Guard. The local connection conditions will possibly necessitate means for the pur- pose of reducing the surge currents upon switching the pump on. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 42: Star/Delta Start-Up Circuit

    The mains supply must match the mains power rating of the motor. In the connection area expect temperatures of up to 90 °C. The connection line must be rated for these temperatures. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 43 Installation Star / Delta ∆ 18,5 17,3 16,2 15,0 ∆ Voltage Spannung 50 Hz Delta ∆ ∆ Voltage 60 Hz Spannung Diagram 1 Voltage/current diagram GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 44 Dauerbetrieb! 3~ / 460 V (60 Hz) continuous operation is allowed! Continuous 3~ / 690 V (50 Hz) operation For 60 Hz not possible Fig. 3.3 Mains connection (figures in the junction box ) GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 45 Observe the direction of rotation of the running down fan. The correct direc- tion of rotation is indicated by an arrow in the junction box. In the case of a wrong connection, rewire. Close the housing again. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 46: Power Failure

    The Pt 100 measures the temperature of the oil: ■ upstream of the oil cooler in the case of the air cooled pumps downstream of the heat exchanger in the case of water cooled pumps. ■ GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 47: Connecting The Cooling Water

    Only at an oil temperature of approximately 40° C will the thermostat open and the cooling water flow. At 20° C this takes approximately 10 minutes. Cooling water throughput may vary between 0 and 12 litres per minute depending on the temperature of the cooling water. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 48 SP-Guard Note the lettering! Quick locks for opening the fan cover Supply Connections cooling water Return G 1/2” Correctly connect the cooling water! Fig. 3.4 SP 630 F - Connection of the cooling water GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 49: Water Quality

    DS water (softened or fully desalinated water) can be used for cooling the pump, if the pH value corresponds to the range indicated above. Materials in the cooling circuit of the pump: AISI 304, AISI 316, copper sol- der, brass GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 50 24 V DC 2.5 W 2,5 W max. 3,4 W max. 3.4 W Oil tempera ture Öltemperatur- sensor sensor Oil level Ölstand- schalter switch Fig. 3.5 Block diagram for the screw pump with accessories GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 51: Connecting The Sp-Guard

    Switching output S1 (warning) red/blue Switching output S2 (error) white/green Switching output S3 (watchdog) brown/green Switching output S4 (pump on) yellow/brown 0 V (GND for PLC controller) Not connected Shield For connection, see fig. 3.7 GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 52 1 V below the power supply voltage level and the low level is at approximately 1 V. The maximum current rating is 40 mA. The outputs are protected by means of semiconductor fuses. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 53 Warning limit, vibrations digits Failure limit, vibrations 0,2 s Hysteresis, vibration meas. °C Warning limit, oil temperature Failure limit for ATEX operation °C Failure limit, oil temperature for non-ATEX operation digits “Pump on” threshold GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 54: Connecting The Electro-Pneumatic Gas Ballast Valve

    The non-return valve has been glued in ensuring a tight seal. Unscrew the union nuts (30 mm spanner) and remove the manual gas ballast actuator. Reassemble the entire unit with the solenoid actuator. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 55: Connecting The Purge Gas Valve

    Fig. 3.13 Electrical connections at the purge gas valve Purge gas connection - G 1/8" inside thread Loosen screw and pull the plug Fig. 3.14 Connecting the plug and the purge gas at the purge gas valve GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 56: Operation

    When doing so make sure that all aids used are clean so as to avoid con- taminating the oil. Use only lubricating oil which has been approved by Leybold. The gear oil should be filled in at room temperature. At lower temperatures, the oil is thicker so that there then is the risk of overfilling gear chamber with oil.
  • Page 57 6 Oil level mark ”Minimum” 7 Ground contact Minimum mark Oil level at the oil sight glass Float Fig.4.1 Oil level, oil sight glass and junction box (pump with covers removed) GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 58 Verkleidungshälfte Left cover section on the = Verschluss-Schrauben (9 Stück) der Serviceseite service side Closure screws (9 pieces) Fig. 4.3 Unlocking the closure screws and removing the divided cover section GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 59 Thermostat settings 4 and 5 must not be set up since damage may occur NOTICE due to inadequate cooling. At water temperatures exceeding 25° C the thermostat will no longer be able to maintain a constant oil temperature. The air cooling share will then increase. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 60: Operation

    Press the pushbutton - long (3 seconds), and then short twice. A confirmation of the resetting pro- cess will be indicated on the display for approximately 5 seconds. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 61: Gas Ballast Operation

    Observe safety informations 0.4.4 and 0.4.5. Manually operated gas ballast valve A 90° turn of the knob will suffice for completely actuating the gas ballast valve, the gas ballast valve is either open or closed, see fig. on top. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 62: Purge Gas Operation

    Therefore the SP Guard displays an error message when the pump is at a standstill and there is no gas flow. Thus we recommend the fol- lowing power-off sequence: pump, SP Guard, purge gas. Switch on the pump in reverse order. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 63: Regular Checks

    If much condensate is col- lected, the condensate separator will have to be checked regularly. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 64: Switching Off/Shutting Down

    Section 2 “Storing”. For this please contact Leybold for advice. Depending on the pump version switch off power supply for the SP-Guard ■...
  • Page 65: Maintenance

    All work within the pump should be left to suitably trained staff. In this con- text we would like to inform you about practical seminars offered by Leybold in which maintenance, repair and testing of the SP 630 are cov- ered by qualified instructors. Improperly performed maintenance or repair work will void the CE and ATEX conformity and void any warranty claims.
  • Page 66: Checking The Oil Level

    When disposing of the waste oil observe the applicable environment pro- tection regulations. NOTICE Use only lubricants approved by Leybold. To change the oil, the cover section on the discharge side needs to be disas- sembled, see fig. 4.2 or 4.3.
  • Page 67 3. Check the oil level once more and remove possibly escaped oil from the bottom trough. 4. It is to be expected that the pump will continue to lose small quantities of oil from the drain openings. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 68: Cleaning The Oil Cooler

    Cleaning the Dust Filter in the Intake Line (optional) The dust filters which are installed upstream of the pump need to be checked regularly for contamination and cleaned as required. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 69: Water Filter Maintenance

    A calcification of the heat exchanger may also result in a reduced cooling performance. In such a case the heat exchanger will have to be replaced. The heat exchanger must not be treated with a decalcifier. NOTICE GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 70: Checking And Cleaning The Gas Ballast Filter

    Removing the pump’s cover (see Fig. 4.2 or 4.3). Pull the hose lines off from the throttles at the gear housing. Press the ring against the plug-in connection and pull the hose line off. Unscrew both throttles. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 71 Check to see that gas comes out at both new throttles. The flowing gas must be easily audible. Close the switch-on valve (de-energise). Pull the hose lines off from the throttle (press the ring against the connector). GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 72: Service At Leybold

    Fit the pump cover again. Service at Leybold If you send a pump to Leybold indicate whether the pump is free of sub- stances damaging to health or whether it is contaminated. If it is contaminated also indicate the nature of the hazard. To do so, you must use a preprinted form which we shall send to you upon request.
  • Page 73: Maintenance Schedule

    Instructions Ruvac adapt- (elastic parts) er (replace elastic parts only if defective) Purge gasket, function test, after or 2.5 years Operator, on site EK 110000827 See Operating replace purge gas connection Instructions purge gas kit GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 74: Troubleshooting

    Display is dark and Ambient temperature is too high. Let the SP-GUARD cool down and keep the Operator difficult to read. ambient temperature below 40 °C. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 75 Fit a valve to shut off the intake port. the presence of (automatically upon pump standstill). a vacuum the pressure in the Valve at the intake port is not closed. Close the valve at the intake port. system increases too rapidly. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 76 No need for action. junction box. Purge gas Valve has not switched. Check valve, if required connect correctly. Electrician gauge does not Purge gas supply has failed. Ensure a proper purge gas supply. indi cate any pressure. GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 77: Waste Disposal

    Waste oil from vacuum pumps must not be mixed with other substances or materials. Waste oil from vacuum pumps (Leybold oils which are based on mineral oils) which are subject to normal wear and which are contaminated due to the influence of oxygen in the air, high temperatures or mechanical wear must be disposed of through the locally available waste oil disposal system.
  • Page 78: Ec Declaration Of Conformity

    EC Declaration of Conformity GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 79 GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 80 Person to contact: Calibration: Factory-calibr. Phone : Fax: Quality test certificate DIN 55350-18-4.2.1 End user: A. Description of the Leybold product: Failure description: Material description : Catalog number: Additional parts: Serial number: Application-Tool: Type of oil (ForeVacuum-Pumps) : Application- Process: B.
  • Page 81: Index

    54, 55, 59, 61, 63, 64, 70, 73, 75 Overpressure 6, 7, 9, 18 Gas ballast valve 28, 30, 54, 61, 63, 70 Ground connection 19, 51, 73 Heat exchanger 23, 46, 47, 64, 69, 74, GA02411_002_C0 - 10/2016 - © Leybold...
  • Page 82 Sales and Service Germany Great Britain America Leybold Japan Co., Ltd. Tsukuba Technical Service Center 1959, Kami-yokoba Leybold UK LTD. Leybold GmbH Tsukuba-shi, Ibaraki-shi 305-0854 Unit 9 Sales, Service, Support Center (3SC) Japan Silverglade Business Park Bonner Strasse 498 Leybold USA Inc.

Table of Contents

Save PDF