Bmk 1500/2000 Combustion Cal Menus; Bmk 2500/3000 Combustion Cal Menus - Watts AERCO Benchmark OMM-0127 Operation And Maintenance Manual

Natural gas fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Boiler Operation & Maintenance Manual - KOREA
SECTION 2: OPERATION

2.8.2 BMK 1500/2000 COMBUSTION CAL Menus

TABLE 2-7: COMBUSTION CAL Menu: BMK 1500/2000
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 18%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level

2.8.3 BMK 2500/3000 COMBUSTION CAL Menus

TABLE 2-8: COMBUSTION CAL Menu: BMK 2500/3000
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 14%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
OMM-0128 • GF-206-K
• 5/9/2019
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0%
100%
Displays current value
0
10.00 V
Displays current value
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0%
100%
Displays current value
0
10.00 V
Displays current value
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DEFAULTS
BMK 1500
BMK 2000
1.80
1.40
2.30
3.80
2.50
4.30
2.90
5.40
3.80
6.40
7.90
9.50
Variable
2.00 V
2.00 V
DEFAULTS
BMK 2500
BMK 3000
2.20
2.80
4.10
4.60
4.80
5.00
5.30
5.50
6.80
6.90
8.50
9.10
Variable
2.00 V
2.00 V
Page 22 of 146