Appendix A: Boiler Menu Item Descriptions - Watts AERCO Benchmark OMM-0127 Operation And Maintenance Manual

Natural gas fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Boiler Operation & Maintenance Manual - KOREA
APPENDIX A: BOILER MENU DESCRIPTION

Appendix A: BOILER MENU ITEM DESCRIPTIONS

TABLE A-1: Operating Menu Item Descriptions
See Section 2-4 OPERATING Menu for a range of choices and the default values.
TABLE A-1: OPERATING Menu Item Descriptions
MENU OPTIONS
1
Active Setpoint
2
Outlet Temp
3
Inlet Temp
4
Air Temp
5
Outdoor Temp
6
Valve Position In
7
Valve Position Out
8
FFWD Temp
9
Exhaust Temp
10
Flame Strength
11
Min Flame Str
12
O2 Monitor
13
Oxygen Level
14
Ignition Time
15
SSOV Time to OPN
16
Spark Current
17
Run Cycles
18
Run Hours
OMM-0128 • GF-206-K
• 5/9/2019
This is the setpoint temperature to which the control is set when
operating in the Constant Setpoint, Remote Setpoint or Outdoor
Reset Mode. When in the Constant Setpoint Mode, this value is
equal to the Internal Setpoint setting in the Configuration Menu.
When in the Remote Setpoint Mode, this value is the setpoint
equivalent to the remote analog signal supplied to the unit.
When in the Outdoor Reset Mode, this is the derived value from
the charts in Appendix E.
Displays the outlet water temperature.
Displays the inlet water temperature.
Air Temp is the air temperature at the input to the Air/Fuel Valve.
This reading is one of the parameters used to control the Blower
Motor speed.
Outdoor temperature is displayed in ºF or ºC, only if outdoor
temperature sensor is installed and enabled.
Desired input valve position. This would normally be the same
as the fire valve position shown on the bar graph (valve position
out) when the boiler is operating.
Displays actual real time Valve Position.
Displays BST header temperature
Displays the exhaust temperature in °F (default) or ºC.
Displays flame strength from 0% to 100%.
Not Used
Enables or disables the O2 Monitor.
Displays the real-time combustion oxygen (O
measured by the O
sensor.
2
Displays the elapsed time between confirmation of gas valve
opening (POC) until a stable flame is detected.
Displays the elapsed time between 120VAC being applied to the
Gas Valve and confirmation of gas valve opening (POC).
Displays the current going to the ignition transformer.
Displays the total number of run cycles.
Displays total run time of unit in hours.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DESCRIPTION
) level (%)
2
Page 71 of 146