9.2 Basic configuration
9.2.1 Quick wizard: Language / time and date
9.2.2 Quick wizard: Standard
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
5 Proceed with the configuration of the system. When done, confirm the
configuration settings.
Result: The screen shortly turns OFF and Busy is displayed for several seconds.
#
Code
[A.1]
N/A
[1]
N/A
Space heating settings
The system can heat up a space. Depending on the type of application, the space
heating settings must be made accordingly.
Space heating: Unit control method
#
Code
[A.2.1.7]
[C-07]
LWT control:
Unit operation is decided based on the leaving water temperature regardless the
actual room temperature and/or heating demand of the room.
Ext RT control:
Unit operation is decided by the external thermostat or equivalent (e.g. heat pump
convector).
RT control:
Unit operation is decided based on the ambient temperature of the user interface.
Space heating: User interface location
#
Code
[A.2.1.B]
N/A
Only applicable if there are 2 user interfaces (1 installed in the room, 1 installed at
the indoor unit).
Description
Language
Time and date
Description
Unit control method
▪
0 (LWT control)
▪
1 (Ext RT control)
▪
2 (RT control)
Description
User interface location
▪
0 (At unit)
▪
1 (In room)
9
Configuration
|
Installer reference guide