10.4.3 To perform a test run

10.4.4 To perform an actuator test run

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 97].
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Automatic and press
4 Go to [A.7.3.4]
purge > Start air purge and press
Result: Air purging will start and the following screen will be shown.
INFORMATION
The test run only applies to the additional temperature zone.
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 97].
2 Go to [A.7.1]:
> Installer settings > Commissioning > Test run.
3 Select a test and press
4 Select OK and press
Result: The test run starts. It stops automatically when done (±30 min). To stop it
manually, press
, select OK and press
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
The user interface used to start the test run displays a status screen.
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select Pump, a test run of the pump will start.
Purpose of the actuator test run is to confirm the operation of the different
actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 97].
2 Go to [A.7.4]:
> Installer settings > Commissioning > Actuator
test run.
3 Select an actuator and press
4 Select OK and press
Result: The actuator test run starts. It automatically stops when finished. To stop it
manually, press
, select OK and press
.
> Installer
settings > Commissioning > Air
to start the air purge function.
. Example: Heating.
.
.
. Example: Pump.
.
.
10
Commissioning
|
"To set the user permission level
> Installer
settings >
"To set the user permission level
"To set the user permission level