Mounting - Smoke vent button RT 45-L-RJ / RT 45-RJ

- The smoke vent button (RT 45L-RJ / RT 45-RJ)
can be used to initiate manual venting and reset
an alarm.
- Up to 8 smoke vent buttons can be connected in
series.
- Smoke monitoring of the main evacuation level is
provided by a point detector, which can be
connected directly to the RT 45-RJ.
- A monitoring resistor is used to monitor the line.
- Only if another smoke vent button or a point
detector is connected to the RT 45-RJ, the PCB
jumper J1 must be removed.
- Connect the smoke vent button to the „RT" socket
on the central unit.
AL
COM 1
COM 2
SD
RT
ADD
Operation OK
Alarm
OK
... -LT
Ventilation OPEN
99.829.07 1.2/06/23
<or>
24 V
M1
Fault
ALARM
RESET
* Central unit is only partially operational, contact customer service.
** Flap cannot be closed by manual ventilation button.
RT 45-RJ
1
RT
> 1
RT
1 RT + Smoke
detector
> 1
RT
+ Smoke
detector
green
red
yellow
blue
= LED does not light up
English
RT 45-L-RJ
J1
Do not remove J1
Last RT:
Do not remove J1
All other RTs:
remove J1
remove J1
All Ts:
R
remove J1
Description
System "OK"
Fire alarm
Fault*
Hygienic ventilation:
Manual opening (ventilation button)
Automatic opening (RTR)
Emergency ventilation**:
Ventilation alarm, radio connection disturbed
Shaft temperature too high
= LED lights up
= LED flashes
AIO Basic