7
|
Unit installation
7.4 Mounting the indoor unit
7.4.1 About mounting the indoor unit
7.4.2 Precautions when mounting the indoor unit
7.4.3 To install the indoor unit
Installer reference guide
68
D Drain holes
E Knockout hole for snow
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface,
raise the unit to provide a free space of more than 150 mm under the outdoor unit.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1
Installing the indoor unit.
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
General safety precautions
▪
Preparation
1 Lift the indoor unit from the pallet and place it on the floor. Also see
handle the indoor
2 Connect the drain hose to the drain. See
4
the
drain" [
69].
3 Slide the indoor unit into position.
4 Adjust the height of the leveling feet to compensate for floor irregularities.
The maximum allowed deviation is 1°.
unit" [
4
25].
"7.4.4 To connect the drain hose to
≤1°
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
"4.3.3 To