Boiler efficiency
Depending on the used boiler, this should be chosen as follows:
#
Code
[9.C.2]
[7‑05]
Alarm output
#
Code
[9.D]
[C–09]
Alarm output logic
[C-09]
0
Closed output
1
Open output
Auto restart
When power returns after a power supply failure, the auto restart function
reapplies the user interface settings at the time of the power failure. Therefore, it
is recommended to always enable the function.
User settings > Electricity price >
Medium
User settings > Electricity price >
Low
User settings > Gas price
0: Very high
1: High
2: Medium
3: Low
4: Very low
Alarm output: Indicates the logic of alarm
output on digital I/O PCB during high level indoor
unit error malfunctioning. Low level errors
(caution/warning) will NOT be transmitted to
alarm output.
0 Abnormal: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
1 Normal: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).
Alarm
No alarm
Open output
Closed output
10
Configuration
|
Description
Description
Description
No power supply
to unit
Open output
Installer reference guide
165