5.5.3

Blast tube length

The length of the blast tube must be selected according to the in-
dications provided by the manufacturer of the boiler, and in any
case it must be greater than the thickness of the boiler door com-
plete with its refractory.
The lengths L available are:
Blast tube
RS 160-200/E BLU
5.6

Positioning probe - electrode

Before fixing the burner to the boiler, check from
the opening of the blast tube that the probe and
the electrode are correctly positioned, as in
Fig. 16.
WARNING
If, in the previous check, the position of the probe or electrode
was not correct, is necessary:
 remove the screw 1)(Fig. 15)
 extract the inner part 2)(Fig. 15) of the head, and adjust
them.
Do not rotate the probe: leave it as in Fig. 16.
If it is located too close to the ignition electrode,
the control box amplifier may be damaged.
WARNING
Observe the dimensions shown in Fig. 16.
WARNING
Short (mm)
Long (mm)
373
503
Probe
D1209
Installation
For boilers with front flue passes 13)(Fig. 17 at page 24), or flame
inversion chambers, a protection in refractory material 11) must
be inserted between the boiler refractory 12) and the blast tube
10).
This protection must not compromise the extraction of the blast
tube.
For boilers with a water-cooled frontal, a refractory cover is not
necessary 11)-12)(Fig. 17), unless expressly requested by the
boiler manufacturer.
Tab. L
1
2
Electrode
23
GB
D7951
Fig. 15
Fig. 16
20067467