Measuring The Ionisation Current; Checking The Air And Gas Pressure On The Combustion Head - Riello RS 160/E BLU Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

7.2.5

Measuring the ionisation current

The burner is fitted with an ionisation system to check that a
flame is present.
The minimum current for control box operation is 4 µA. The Op-
erator Panel visualises "30%" (see "Parameter list" at page 46,
parameter no. 954).
The burner provides a much higher current, so controls are not
normally required.
However, if it is necessary to measure the ionisation current, dis-
connect the plug-socket on the ionisation probe cable and insert
a direct current microammeter with a base scale of 100 µA - see
Fig. 38.
Carefully check the polarities!
WARNING
7.2.6
Checking the air and gas pressure on the
combustion head
To carry out this operation a pressure gauge must be used to
measure the air and gas pressure at the combustion head, as
shown in Fig. 39.
20067467
Maintenance
Checking
gas pressure
D7893
54
GB
D7894
Checking
air pressure
Fig. 38
Fig. 39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 200/e blu200895252013489920169809

Table of Contents