Download Print this page

Kohler 48RCLB/C Operation page 15

Residential/light commercial generator sets

Advertisement

To ensure continued satisfactory operation perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for obstructions that could block the
flow of cooling air. Keep the air intake area clean. Do not
leave rags, tools, or debris on or near the generator set.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Coolant Level. Check the coolant level according to the
cooling system maintenance information.
Note: Block heater damage. The block heater will fail if
the energized heater element is not immersed in
coolant. Fill the cooling system before turning on
the block heater. Run the engine until it is warm,
and refill the radiator to purge the air from the
system before energizing the block heater.
Drive Belt(s). Check the belt condition of the water
pump and battery charging alternator belt(s).
Exhaust System. Check for exhaust leaks and
blockages. Check the silencer and piping condition and
check for tight exhaust system connections.
Inspect the exhaust system components for cracks and
corrosion (exhaust manifold, exhaust pipe, exhaust
clamps, and silencer).
Check for corroded or broken metal parts and replace
D
them as needed.
Check that there are no combustible materials near
D
the exhaust outlet.
Check that the exhaust outlet is unobstructed.
D
Carbon
Monoxide
Detectors.
installation and operation of carbon monoxide (CO)
detectors on each level of any building near the
generator set.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
2.3 Exercising the Generator Set
Operate the generator set every week or every other
week for 20 minutes. Perform all of the prestart checks
before starting the exercise procedure. See Section 2.5
for instructions to set the automatic exerciser.
TP-7102 9/21
2.4 Generator Set Operation
2.4.1
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.2
An automatic transfer switch monitors the utility power
and signals the generator set to start when utility power
is lost. The ATS then transfers the load to the generator
set.
When utility power is restored, the transfer switch
transfers the load back to utility, runs the generator set
with no load to cool down the engine, and then stops the
generator set engine. The electric fans continue to run
for two minutes after the engine shuts down to evacuate
the engine compartment.
2.4.3
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.4
The controller attempts to start the generator set three
Check
for
the
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an overcrank
fault. See Section 2.6.
Pressing the OFF button during the crank cycle stops
the cranking. No other buttons are acknowledged during
the crank cycle.
2.4.5
The engine cooldown time delay allows the engine to
run after the loads have been removed.
Local Starting and Stopping
Automatic Starting and Stopping
Remote Starting and Stopping
Engine Start Crank Cycle
Engine Cooldown
Section 2 Generator Set Operation
15

Advertisement

loading

This manual is also suitable for:

60rcla/b