MAINTENANCE PROGRAM
REMOVING
THE BLAST TUBE
POSITION OF ELECTRODES
ATTENTION:
Check the position of the
electrodes after any
intervention as wrong
position could cause
ignition troubles.
GAS FILTER CLEANING - GAS PILOT FILTER CLEANING
24
www.eacoon.com
5
10
min. 6
µA
LANDIS LFL1.622
LANDIS LFL1.333
Microammeter
50 µA end of scale
Elettrodo
Ignition Electrode
accensione
Ionization Probe
Elettrodo
rivelazione
The ionization current is checked by inserting a microammeter with
an end scale of 50 µA (d.c.) in series with the ionization probe.
A faulty position of the electrode can lead to a reduction in the
24
ionization current and cause a safety shut off of the burner due to
a flame detection failure. In this case, check the position of the
electrode, its electric connection and the earthing of the burner.
The ionization current is normally > 20 µA.
Check and clean the gas filter
in the pilot gas valve
REMOVING
THE FIRING HEAD
420010511800