Setting of system type

number
- Remove the black cover plate.
- Set the position selector (f) on 0.
- Press the + key (d) twice.
The display will now change between
P0.2 and a number between 0 and 6.
- With a pointed object, press the SET
key (i). The number will begin to flash.
- Press either the + or - key (d or e)
until the display shows the required
system type number.
- Press the SET key (i) to store the
required system type number.
- Refit the black cover plate.
Control operates according to factory-
set values.
Note
If the factory-set values in the control
are to be changed, see the pages 13-48
or contact Danfoss.
Display of actual temperature
8
Actual temperature (hot water, flow or
room temperature) can be read off with
the function selector (f) on (pos. 7).
Setting required normal temperature
Set the position selector (f) on
8). The temperature can be increased or
reduced by pressing the + or - key.
Setting required reduced temperature
Set the position selector (f) on
9). The temperature can be increased or
reduced by pressing the + or - key.
VI.72.M4.02 © Danfoss 11/97
(pos.
(pos.
BC-HM