Airwell OU-PSINV-70TH Installation Instructions Manual page 57

Dc inverter air conditioner
Table of Contents

Advertisement

10-16-3. Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2,...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
10s
20s
DIP switch
ON
ON
OFF
1
2
8 – 10 HP
OC (CN500, BLU)
63PH (CN027, WHT)
FUSE (0.5A, F500)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
FUSE
(6.3A, F101)
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
N . P . C H E C K
LED2
(CN046, RED)
R.C.ADD. Rotary switch
MODE (CN038)
System address
No.
0 Automatic address
(Setting at shipment = "0")
1 (If outdoor unit is No. 1)
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30 (If outdoor unit is No. 30)
Big_PAC_eng.indb 57
Big_PAC_eng.indb 57
8 – 10 HP
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
TO (CN023, BLK)
TD (CN024, BLK)
MOV1
(CN300, WHT)
MOV2
(CN301, BLK)
LED (D041)
EEPROM
TEST (CN033, RED)
LED1
C-CHK (CN035)
A.ADD (CN047)
R.C.ADD. DIP switch
IC001
D115
Fig. 10-13
System address
System address
10s digit
1s place
(2P DIP switch)
(Rotary switch)
Both OFF
"0" setting
ON
ON
1
2
OFF
Both OFF
"1" setting
ON
ON
1
2
OFF
Both OFF
"2" setting
ON
ON
1
2
OFF
10s digit ON
"1" setting
ON
ON
1
2
OFF
20s digit ON
"1" setting
ON
ON
1
2
OFF
10s digit and 20s
digit ON
"0" setting
ON
ON
1
2
OFF
10-16-4. Automatic address setting from the outdoor unit
When there are multiple outdoor units as shown in basic wiring
diagram 2
If the power can be turned ON separately for the indoor and
outdoor units in each system (indoor unit addresses can be
set without operating the compressor):
(1) Turn ON the indoor and outdoor unit power for refrigerant
system 1.
Press and hold the automatic address setting button
(black) for 1 second or longer at the outdoor unit where the
power was turned ON.
Communication for automatic address setting begins. LED
1 and 2 on the outdoor unit control PCB blink alternately,
and turn OFF when address setting is completed.
(2) Next, turn ON the power only at the indoor and outdoor
units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed. Repeat the same procedure for each system
and complete automatic address setting.
(3) Operation using the remote controller is now possible.
10-16-5. Indoor unit remote controller main-sub setting
● When multiple wall-mounted indoor units are installed for
group control in a simultaneous-operation multi system, set
the control PCB at the No. 2 and following wall-mounted
units to "Sub remote control".
If a wired remote controller is used, set the wired remote
controller to "Sub".
If 2 wireless remote controllers are used, set the wireless
PCB (DIP switch) on the second remote controller to "Sub".
57
<Approximately 4 – 5
minutes are required.>
2009/08/26 16:33:22
2009/08/26 16:33:22

Advertisement

Table of Contents
loading

Table of Contents