Heat Pump Systems - Braeburn PREMIER Series Installer's Manual

Non-programmable thermostats, up to 2 heat / 1 cool heat pump 1 heat / 1 cool conventional, up to 3 heat / 2 cool heat pump, up to 2 heat / 2 cool conventional
Hide thumbs Also See for PREMIER Series:
Table of Contents

Advertisement

Heat Pump Systems

Typical Wiring Configurations
NOTE: The "System Type" option will be configured in the Installer Settings section. Shaded areas do not
apply to the 3020.
1 HEAT / 1 COOL - No Auxiliary Heat
Set System Type to 11HP
Rh 24 Volt AC Power
Rc Connected to Rh with supplied Jumper Wire
O/B Changeover Valve [note 2]
Y1 Compressor Relay
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 21HP (3020 Only)
Rh
24 Volt AC Power
Rc
Connected to Rh with supplied Jumper Wire
O/B Changeover Valve [note 2]
Y1
Compressor Relay (1st stage heating/cooling)
E
Auxiliary/Emergency Heat Relay [note 6]
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 22HP (3220 Only)
Rh 24 Volt AC Power
Rc Connected to Rh with supplied Jumper Wire
O/B Changeover Valve [note 2]
Y1 Compressor Relay (1st stage heating/cooling)
W2 Auxiliary Heat Relay (2nd stage heating) [note 3]
E
Emergency Heat Relay [note 3]
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
L
Optional System Fault Monitor [note 4]
Additional Wiring Options
NOTE: Additional options are configured in the
Installer Settings section.
S1
Indoor or Outdoor Remote Sensor [note 1]
S2
Installer Guide
2 HEAT / 2 COOL - No Auxiliary Heat
Set System Type to 32HP (3220 Only)
Rh 24 Volt AC Power
Rc Connected to Rh with supplied Jumper Wire
O/B Changeover Valve [note 2]
Y1 Compressor 1 Relay (1st stage heating/cooling)
Y2 Compressor 2 Relay (2nd stage heating/cooling)
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
L
Optional System Fault Monitor [note 4]
3 HEAT / 2 COOL – Including Auxiliary Heat
Set System Type to 32HP (3220 Only)
Rh
24 Volt AC Power
Rc
Connected to Rh with supplied Jumper Wire
O/B
Changeover Valve [note 2]
Y1
Compressor 1 Relay (1st stage heating/cooling)
Y2
Compressor 2 Relay (2nd stage heating/cooling)
E/W3 Auxiliary Heat Relay (3rd stage heating) [note 5]
G
Fan Relay
C
24 Volt AC Transformer Common [note 1]
L
Optional System Fault Monitor [note 4]
NOTES - Heat Pump Systems
[1] Optional 24 Volt AC common connection.
[2] O (cool active) or B (heat active) is selected in
the Installer Settings menu.
[3] Install a field supplied jumper between the
W2 and W1/E/W3 terminals if there is
no separate emergency heat relay installed.
[4] If the L terminal is used, the 24 Volt AC common
must be connected (C terminal).
[5] If a separate emergency heat relay is installed, the
W1/E/W3 terminal should have both the auxiliary
heat 1 relay and emergency heat relay connected.
[6] If a separate emergency heat relay is installed, the
W1/E terminal should have both the auxiliary
heat 1 relay and emergency heat relay connected.
Provide disconnect and overload protection as required.
NOTES - Additional Wiring Options
[1] These terminals can be used to connect a
Braeburn
indoor or outdoor remote sensor.
®
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

30203220

Table of Contents