Removing A Pro Device - Siemens SIMATIC HMI IFP Operating Instructions Manual

Industrial flat panels
Table of Contents

Advertisement

Installing and connecting the device
3.5 Removing the device
3.5.2

Removing a PRO device

The HMI deices is generally removed by following the steps taken to install in it but in the
reverse order.
Procedure
Proceed as follows:
1. Close all open programs on the PC which is connected to the Flat Panel.
2. Switch off the power supply to the Flat Panel.
3. When you use the Flat Panel in a hazardous area, make sure that one of the two
following requirements is met: The area is no longer hazardous or the Flat Panel and its
plug-in connections are de-energized.
4. Open the connection bay by removing the connection bay cover.
5. Remove all cable ties that were installed for strain relief of the connecting cables in the
terminal compartment of the Flat Panel.
6. Remove all plug-in connectors and the equipotential bonding cable from the Flat Panel.
7. Remove the Flat Panel from the support arm or pedestal. Make sure that the connection
cables are not damaged.
8. Fasten the terminal compartment cover to the device with the 2 screws, torque 1.5 Nm.
See also
Mounting the PRO device (Page 49)
Connecting the device (Page 56)
72
IFP, IFP PRO, IFP ETH
Operating Instructions, 09/2019, A5E31298376-AJ