RUGGEDCOM i800
Installation Guide
Section 6.1.10
Other Approvals
This device meets the requirements of the following additional standards:
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM i800 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
Other Approvals
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Earth ground ports
Enclosure ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
DC Power ports
Certification
Test Levels
± 4 kV
± 8 kV
± 8 kV
20 V/m
± 4 kV @ 5 kHz
± 4 kV @ 5 kHz
± 1 kV line-to-earth
± 0.5 kV line-to-earth/line
10 V
30 A/m
30% reduction for 0.3 seconds
60% reduction for 1 second
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
10 V Continuous, 100 V for 1 s
10 V Continuous, 100 V for 1 s
± 15%
Chapter 6
23