Samson TROVIS SAFE 3731-3 Mounting And Operating Instructions page 75

Hide thumbs Also See for TROVIS SAFE 3731-3:
Table of Contents

Advertisement

Parameter – Display, values
Code
no.
[default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
28*
Alarm test
Reading direction:
Standard
[No]
RUN 1
RUN 2
RUN 3
ESC
29*
Position transmitter x/ix
[ää]
äæ
ESC
30*
Fault alarm ix
[No] HI LO
ESC
Position transmitter test
31*
–10.0 to 110.0 [default
value is the last indicated
value of the position
transmitter]
% of the operating range
ESC
3)
Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.
Description
Testing the software limit switches alarm A1 and A2 as well as
the fault alarm contact A3.
If the test is activated, the respective limit switches five times.
Turned
RUN1/1 RUN: Software limit switch A1
[No]
RUN2/2 RUN: Software limit switch A2
1 RUN
RUN3/3 RUN: Fault alarm contact A3
2 RUN
3 RUN
ESC
3)
Operating direction of the position transmitter; indicates how the
travel/angle position is assigned to the output signal i, based on
the closed position.
The operating range (see Code 8) of the valve is represented by
the 4 to 20 mA signal.
When a positioner is not connected (reference variable less than
3.6 mA), the signal is 0.9 mA and when the positioner has not
been initialized 3.8 mA.
3)
Used to select whether faults causing the fault alarm contact to
switch should also be signaled by the position transmitter output
and how they should be signaled
HI ix = 21.6 mA or LO ix = 2.4 mA
3)
Testing the position transmitter. Values can be entered in relation
to the operating range.
The current actual value is used in initialized positioners locally
as the start value (bumpless changeover to the test mode). On
testing over software, the entered simulation value is issued as
the position feedback signal for 30 seconds.