Samson TROVIS SAFE 3731-3 Mounting And Operating Instructions page 57

Hide thumbs Also See for TROVIS SAFE 3731-3:
Table of Contents

Advertisement

Select initialization mode:
→ Code 6
Turn
Press
→ SUB
Turn
Press
to confirm the SUB initialization
mode.
Enter direction of action:
→ Code 7
Turn
Press
, Code 7 blinks.
→ Direction of action (ää/äæ)
Turn
Press
Deactivate travel limit:
→ Code 11
Turn
Press
, Code 11 blinks.
→ No
Turn
Press
Initialization mode
Default: MAX
Direction of action
Default: ää
Travel limit
Default: 100.0
Change pressure limit and control parame-
ters:
Note: Do not change the pressure limit
(Code 16). Only change the control param-
eters K
(Code 17) and T
P
settings of the replaced positioner are
known.
→ Code 16/17/18
Turn
Press
, Code 16/17/18 blinks.
Turn
and set the selected control param-
eter.
Press
to confirm setting.
Enter closing direction and blocking posi-
tion:
Start-up – Settings
(Code 18) if the
V
Pressure limit
Default: No
KP stage
Default: 7
TV stage
Default: 2
Closing direction
Direction of rotation causing
the valve to move to the
CLOSED position (view onto
positioner display)
Default: CCL (counterclock-
wise)
EB 8387-3S EN
57