Product Specifications

100%
75%
Proportional
50%
On/Off/Jog
25%
50°F
75°F
100°F
10°C
24°C
38°C
Ambient Temperature
Introduction
This document provides necessary information for set-up, calibration, testing and use of the P Series quarter-turn
electric actuators stated on the cover page. Each unit is shipped from the factory with initial calibration of mechanical
stops, cams and switches completed for 0-90 degree operation. However, these are general settings and serve as
a starting point for proper calibration of the actuator in its real-world application.
Safety
Safety is a basic factor any time you maintain and operate mechanical equipment. Appropriate handling methods
and proper use of tools and clothes can help prevent serious accidents -- accidents which can cause injuries
to you or a fellow worker. This manual was created to enable a trained user to install, adjust and troubleshoot
your ProMation actuator.
Only competent and trained personnel should install, maintain and operate ProMation Actuators. Any work
related to this actuator must be carried out in accordance with this manual and related codes and regulations.
Local workplace health and safety rules should always be followed.
Duty cycle
Duty cycle is the percent of time that an actuator spends running as a fraction of the total time. Duty Cycle is
directly related to heat; excessively repositioning an actuator typically results in motor overheating which can
cause permanent damage and/or reduced service life.
Duty cycle can be calculated as follows:
(example P2 series actuator running 3 seconds ON and 30 seconds OFF)
Runtime = 3s, Total time = 3s + 30s = 33s, therefore this duty cycle would be 9% (3/33)
Additionally, ProMation P series actuators are designed for a maximum of 1200 starts per hour (one start every
3 seconds maximum).
125°F
150°F
52°C
65°C
Page 2 of 14 P1 LV AdVanced Proportional Series
Actuator Specifications
Torque "lb/Nm
Supply Voltage
Max Inrush Current
Running Current
Motor
Runtime (90°@60Hz/vdc)
Runtime (90
@50Hz)
O
Duty Cycle
Motor Starts
Weight
Mechanical Connections
Electrical Entry
Electrical Terminations
Environmental Rating
Manual Override
Control
Actuator Case material
Motor Protection
Ambient Temperature
Operating Range
P1
300"lbs/35Nm
12vac/dc
24vac/dc
2.0A
1.9A
DC Brush Type
15 sec
15 sec
75% maximum
1200 per hour
5lbs/3kg
ISO5211 F03/F05 8pt 14mm
(2) 1/2" NPT
14-18ga
NEMA 4/4X
8mm Socket Drive
Proportional
Aluminum Alloy, Powder coated
230°F/110°C Thermal F* Class
*Totally Enclosed Non-Ventilated Motors
-22°F to +125°F
-30°C to +52°C
1.1A
1.1A

Advertisement

Table of Contents
loading

This manual is also suitable for:

P1-12vn4 dcP1-24vn4 acP1-24vn4 dc