Product Specifications

100%
75%
Proportional
50%
On/Off/Jog
25%
50°F
75°F
100°F
10°C
24°C
38°C
Ambient Temperature
Introduction
The following procedure is to be followed for set-up, calibration, testing and use of the P Series quarter-turn
electric actuators. Each unit is shipped from the factory with initial calibration of cams and switches completed for
0-90 degree operation. However, these are general settings and serve as a starting point for proper calibration
of the actuator in its real-world application. There are no mechanical stops on this model.
Safety
Safety is a basic factor any time you maintain and operate mechanical equipment. Use of proper handling
methods, tools and clothes can help prevent serious accidents -- accidents which can cause injuries to you
or a fellow worker. This manual was created to enable a trained user to install, adjust and troubleshoot your
ProMation P Series actuator.
Only competent and trained personnel should install, maintain and repair ProMation Actuators. Any work related
to this Actuator must be carried out in accordance with this manual and related codes and regulations. Local
workplace health and safety rules should always be followed.
Wire Sizing Chart
Duty cycle
MAX distance between
Duty cycle is the percent of time that an actuator spends running as a fraction of the total time. Duty Cycle is
Actuator and Supply (feet)
directly related to heat; overusing an actuator typically results in motor overheating which can permanently
P1.A
Actuator/
Voltage
damage it. Overheating also consumes more electricity. Generally speaking, the hotter a motor becomes, the
24VAC
Amps
longer 'rest' it needs to cool down so it runs effi ciently.
0.9A
Wire
Gage
18
184
16
289
14
466
125°F
150°F
52°C
65°C
P1.A
24VDC
0.9A
184
289
466
Page 2 of 13 P1.A-24V-ACDC Standard Proportional Series
Actuator Specifi cations
Torque "lb/Nm
Supply Voltage
Max Inrush Current
Running Current
Motor
Runtime (90°@60Hz/vdc)
Runtime (90
@50Hz)
O
Duty Cycle
Motor Starts
Weight
Mechanical Connections
Electrical Entry
Electrical Terminations
Environmental Rating
Manual Override
Control
Actuator Case Material
Motor Protection
Ambient Temperature
Operating Range
P1.A
445"lbs/50Nm
24vac
0.9A
0.8A
DC Brush Type
20 sec
20 sec
75% maximum
1200 per hour
7lbs/4kg
ISO5211 F05/F07 8pt 17mm
(2) 1/2" NPT
14-18ga
NEMA 4/4X
5mm Hex Drive
Proportional
Aluminum Alloy, Powder coated
230°F/110°C Thermal F* Class
*Totally Enclosed Non-Ventilated Motors
-22°F to +125°F
-30°C to +52°C
24vdc
0.9A
0.8A

Hide quick links: