Mitsubishi Electric FR-S540E-0.4K-EC Instruction Manual page 45

Transistorized inverter
Table of Contents

Advertisement

Extended function parameter list
Parameter
Indication
92
PID lower limit
PID action set point for
93
PU operation
94
PID differential time
95
Rated motor slip
Slip compensation time
96
constant
Constant output range
97
slip compensation
selection
Automatic torque boost
98
selection (Motor
capacity)
Motor primary
99
resistance
Name
Used to set the lower limit value for PID
control.
0 to 100%, - - -
Used to set the PID action set point for PU
operation.
0 to 100%
Used to set the differential time for PID
control.
0.01 to 10s, - - -
Used to set the rated motor slip to make
slip compensation.
0 to 50%, - - -
Used to set the response time of slip
compensation.
0.01 to 10s
Used to choose whether slip compensation
is made or not in the constant output range.
0, - - -
You can set the motor capacity and
exercise automatic torque boost control.
When you set "- - -", V/F control is
exercised.
Set the motor capacity used.
The motor capacity should be equal to or
one rank lower than the inverter capacity.
The number of motor poles should be 2, 4
or 6. (Only 4 poles for constant-torque
motor)
Single-motor operation (one motor run by
one inverter) should be performed.
Wiring length from inverter to motor
should be within 30m.
When using a constant-torque motor, set "1" in
Pr. 71.
<Example> For 1.5kW, set "1.5".
0.1 to 3.7kW, - - -
You can set the motor's primary resistance
value. (Normally, this parameter need not
be set.)
0 to 50 , - - -
Description
40
Factory
Setting
- - -
0%
- - -
- - -
0.5s
- - -
- - -
- - -