6021974-UIM-A-1120
ZE036-060 - Without Powered Convenience Outlet (Direct Drive) (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA MCC
208-1-60 24.4 144.2
230-1-60 24.4 144.2
060
(5.0)
208-3-60
16
110
230-3-60
16
110
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
22
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
FLA
FLA
FLA
38
4.4
7.6
0
38
4.4
7.6
0
24.9
4.4
7.6
0
24.9
4.4
7.6
0
Electric Heat Accessory
Model
kW
Stages
Amps
NONE
-
-
E05
4
1
19.2
E07
5.6
1
26.9
E10
8
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
E30
22.2
2
106.7
NONE
-
-
E05
5.3
1
22.1
E07
7.5
1
31.2
E10
10.6
1
44.2
E15
15.9
2
66.2
E20
21.2
2
88.3
E30
29.6
2
123.3
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
E30
22.2
2
61.6
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
E30
29.6
2
71.2
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
42.5
60
42.5
60
43.2
60
57.6
60
81
90
105.1
110
142.9
150
-
42.5
60
42.5
60
48.6
60
64.7
70
92.3
100
119.9
125
163.7
175
-
32
40
32
40
32
40
37.3
45
50.8
60
64.7
70
86.5
90
-
32
40
32
40
32.1
40
41.4
45
57.3
60
73.2
80
98.5
100