6021974-UIM-A-1120
ZE036-072 - Without Powered Convenience Outlet (Belt Drive) (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA MCC
4
208-1-60
24.4 144.2
4
230-1-60
24.4 144.2
208-3-60
16
110
060
(5.0)
230-3-60
16
110
460-3-60
7.8
52
575-3-60
5.7
38.9
208-3-60
19.6
136
230-3-60
19.6
136
072
(6)
460-3-60
9.4
66.1
575-3-60
7.1
55.3
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Electrical data for single phase gas heating units with belt drive is at the end of the electrical data section.
18
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
FLA
FLA
FLA
38
4.4
6.7
0
38
4.4
6.7
0
24.9
4.4
4.3
0
24.9
4.4
4.3
0
12.1
4.4
2.1
0
8.9
4.4
1.9
0
27
4.4
4.3
27
4.4
4.3
13
2.4
2.1
10
4.4
1.9
Electric Heat Accessory
Model
kW
Stages
Amps
NONE
-
-
E05
4
1
19.2
E07
5.6
1
26.9
E10
8
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
E30
22.2
2
106.7
NONE
-
-
E05
5.3
1
22.1
E07
7.5
1
31.2
E10
10.6
1
44.2
E15
15.9
2
66.2
E20
21.2
2
88.3
E30
29.6
2
123.3
NONE
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
E30
22.2
2
61.6
NONE
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
E30
29.6
2
71.2
NONE
-
-
E07
6.8
1
8.2
E10
10.1
1
12.1
E15
13.6
2
16.4
E20
19.5
2
23.5
E30
28.8
2
34.6
NONE
-
-
E10
10.6
1
10.2
E15
15.9
2
15.3
E20
21.2
2
20.4
E30
30.4
2
29.3
None
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
1
33
E20
15.9
2
44.1
E30
22.2
2
61.6
None
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
1
38.2
E20
21.2
2
51
E30
29.6
2
71.2
None
-
-
E07
6.8
1
8.2
E10
10.1
1
12.1
E15
13.6
1
16.4
E20
19.5
2
23.5
E30
28.8
2
34.6
None
-
-
E10
10.6
1
10.2
E15
15.9
1
15.3
E20
21.2
2
20.4
E30
30.4
2
29.3
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
41.6
50
41.6
50
42
60
56.5
60
79.9
80
103.9
110
141.8
150
-
41.6
50
41.6
50
47.4
60
63.6
70
91.2
100
118.8
125
162.5
175
-
28.7
35
28.7
35
28.7
35
33.1
40
46.7
50
60.5
70
82.4
90
-
28.7
35
28.7
35
28.7
35
37.2
40
53.2
60
69.1
70
94.4
100
-
14.1
20
14.1
20
17.8
20
23.1
25
31.9
35
45.9
50
-
10.8
15
15.1
20
21.5
25
27.9
30
38.9
40
-
33.2
45
33.2
45
33.2
45
33.2
45
46.6
50
60.5
70
82.4
90
-
33.2
45
33.2
45
33.2
45
37.3
50
53.1
60
69.1
70
94.4
100
-
16.3
25
16.3
25
17.8
25
23.1
25
32
35
45.9
50
-
12.6
15
15.1
20
21.5
25
27.9
30
39
40
Johnson Controls Ducted Systems
Need help?
Do you have a question about the ZE Series and is the answer not in the manual?