Summary of Contents for Johnson Controls ZY Series
Page 1
Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A York International Corporation, 5005 6231824-UIM-E-0623 York Drive, Norman, OK 73069 www.johnsoncontrols.com 2023-06-19 Johnson Controls Ducted Systems...
Page 2
Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
ZXA7 side duct application (belt drive)... 86 Ignition control board on standby....118 ZY04 to 06 side duct application (direct Call for heat............118 drive)..............87 Combustion air proving........118 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 4
Start up for units equipped for fan energy rating................. 126 Troubleshooting..............128 Charging tables.............. 133 Smart Equipment™ Control board navigation components................139 Start-Up sheet..............140 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Refer to this manual for assistance or for additional information, consult a qualified contractor, installer, or service agency. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 6
Horizontal flow dry bulb economizer field Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or the installed National Gas and Propane Installation Code, CSA B149.1. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
CAUTION This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
G = E-Coat Indoor Coil & Standard Outdoor Coil w/Reheat* H = E-Coat Indoor & Outdoor Coils w/Reheat* *ZY04-12 units in power supply of 208/230/460/575-3-60 options only. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A fire or explosion may result causing property damage, personal injury or loss of life. Preceding installation About this task: Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 10
Use the excess wire available to its full length to drop or mount the RAT sensor in the duct. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Air Conditioning Contractors of America (ACCA). This furnace is not to be used for temporary heating of buildings or structures under construction. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Gas Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSA- Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
All panels must be secured in place when the unit is lifted. The condenser coils should be protected from rigging cable damage with plywood or other suitable material. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A7 (6) 04 (3) 05 (4) 06 (5) A7 (6) 45.0 35.3 08 (7.5) 09 (8.5) 12 (10) 1013 1008 A7 (6) Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 15
Curb rigid 14 in. small footprint Curb rigid 14 in. large footprint Curb rigid 24 in. small footprint Curb rigid 24 in. large footprint Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 16
Figure 11: ZY04 unit dimensions Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 17
Figure 12: ZY05-06 and ZXA7 unit dimensions Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 18
Figure 13: ZYA7 unit dimensions Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 19
Figure 14: ZY08/09 unit dimensions Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 20
Figure 15: ZY12 unit dimensions Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 21
1TB0401 - through the base electrical and • ZY06 through the curb gas • ZXA7 1TB0403 - through the base electrical and gas Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 22
1TB0401 - through the base electrical and through the curb gas 1TB0403 - through the base electrical and gas Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor ductwork must be insulated and water-proofed. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
R-410A compressor lubricants are known to cause long term damage to some synthetic roofing materials. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A or L1 and C or L3 only. Note: The maximum length is measured from the unit to the thermostat and back to the unit. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Typical field power and control wiring Typical power wiring Figure 23: Everyday Thermostat Control (ETC) typical power wiring Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
The 100,000 BTUH Ultra-Low NOx model is factory equipped to operate correctly at altitudes up to 5,400 ft above sea level, without a high altitude kit. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 29
92,000 4,001 to 4,500 54,600 91,000 4,501 to 5,000 54,000 90,000 5,001 to 5,400 53,500 89,200 above 5,400 not allowed not allowed Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
22.3 22.9 11446 16.8 26.6 None — — — 575-3-60 — — — — 11058 14.9 15.4 11458 13.8 13.3 20.4 20.9 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 31
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 33
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 34
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
11446 16.8 28.7 29.3 None — — — 11.4 11.8 575-3-60 — — — 11058 17.1 17.6 11458 13.8 13.3 22.6 23.1 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 36
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 38
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 39
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
21.1 11446 16.8 24.3 24.9 None — — — 575-3-60 — — — — 11058 13.6 14.1 11458 13.8 13.3 19.1 19.6 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 41
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 43
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 44
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
11446 16.8 26.9 27.6 None — — — 10.3 10.7 575-3-60 — — — 11058 15.8 16.3 11458 13.8 13.3 21.3 21.8 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 46
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 48
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 49
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 52
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 53
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
29.4 None — — — 12.3 12.7 575-3-60 5.1 39.5 — — — 11458 13.8 13.3 22.8 23.3 12358 22.1 33.8 34.3 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 55
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 57
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 58
Non-fused disconnect. Verify on the unit nameplate that the disconnect is correctly sized for the application. Units with field installed electric heat kits may exceed the factory installed disconnect amperage rating. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Face area (sq ft) 16.3 16.3 Rows Condenser coil data Fins per in. Tube diameter (in./mm) .63/16 .63/16 Circuitry type 2-pass Microchannel 2-pass Microchannel Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 60
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 61
2-pass Microchannel Face area (sq ft) Rows Fins per in. Evaporator coil data Tube diameter 0.375 0.375 Circuitry type Intertwined Intertwined Refrigerant control Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 62
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 63
2-pass Microchannel Face area (sq ft) Rows Fins per in. Evaporator coil data Tube diameter 0.375 0.375 Circuitry type Intertwined Intertwined Refrigerant control Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 64
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 65
Drive type Direct Direct Condenser fan data Quantity of motors Motor hp each No. speeds 1,085 1,085 Nominal total cfm 7,600 7,600 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 66
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 1st Stage 60% of 2nd Stage. 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 67
Drive type Direct Direct Condenser fan data Quantity of motors Motor hp each No. speeds 1,085 1,085 Nominal total cfm 8,200 8,200 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 68
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 69
Drive type Direct Direct Condenser fan data Quantity of motors Motor hp each No. speeds 1,085 1,085 Nominal total cfm 8,600 8,600 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 70
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 71
Condenser fan data Quantity of motors Motor hp each 1 1/2 1 1/2 No. speeds 1,140 1,140 Nominal total cfm 7,700 7,700 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 72
MagnaDRY reheat option is available in power supply of 208/230/460/575-3-60 options only. 2 in. throwaway, standard, MERV 4 (Minimum Efficiency Reporting Value). Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Quantity of motors Motor hp each Number of speeds 900 / 1,150 900 / 1,150 Nominal total cfm 3,600 / 4,600 3,600 / 4,600 Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Low, ULN 1500 High, ULN 1050 1500 Note: Routing of gas piping must not interfere with the flue or heat compartment access. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A fire or explosion may result causing property damage, personal injury or loss of life. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
2. Horizontal flow application with barometric relief at the point of installation. standard. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A or L1 and C or L3 only. Blower rotation Check for correct supply air blower rotation. If the blower is rotating backwards, the line voltage at the Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
As the altitude or temperature increases, density correction factors are shown in Table 40 and the density of air decreases. In order to use the Figure 29. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 79
BHP requirement. Solution: As in the example above, no temperature information is given so 70°F is assumed. The 1.4 in. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 80
Select the appropriate drive if multiple drives are available for the chosen motor. 8. Determine turns open to obtain the required operation point. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 83
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 84
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 85
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Standard static option with motor rated at 2.4 hp Static option with motor rated at 2.9 hp Static option with motor rated at 3.7 hp Exceeds recommended blower speed Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 89
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 90
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 91
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Blower performance includes gas heat exchangers and 2 in. filters. See static resistance table for additional applications. Note: See rpm selection table to determine required motor sheave setting and to determine the maximum continuous bhp. kW = 0.929 x bhp Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Verify proper sheave alignment; tighten blower pulley and motor sheave set screws after these adjustments. Re-checking set screws and belt tension after 10-12 hrs. run time is recommended. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 97
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Thermostat connection 24 VAC connection Thermostat connection No connection Thermostat connection 24 VAC common For internal use only No connection (For future use) Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 99
Shall be interlocked to the fan relay. (When LIMIT Limit switch power is interrupted from this input, the fan will be forced on by software) Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 100
2nd stage on output will energize. (heat/cool) 1st stage in Rapid flash ASCD (heat/cool) 1st stage on (heat/cool) Fan only (no Fast heartbeat heat/cool) Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 101
2 to 5 seconds: Clear anti-short cycle timers and Factory test mode Rapid flash Rapid flash reset any active lockouts • More than 5 seconds: Clear all fault history Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
SD-24 and R 24 VAC common for thermostat power Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 103
10KΩ at 77°F, type III negative temperature VDC reading EC2+ to EC2– with open circuit. Used in suction line temperature safety. coefficient thermistor Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 104
24 VAC hot output for compressor 2 allow compressor 2 operation; output with compressor cooling, comfort ventilation cooling or heat pump heating demands Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 105
Button for display menu acknowledgment and navigation Button for display menu navigation and zeroing of active compressor CANCEL ASCD timer 4-way Joystick for display menu navigation Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 106
Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
The energizes the compressor and condenser fan motor blower is energized after any specified delay only. associated with the operation. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 108
Should a freezestat open three times within two hours of operation, the UCB will lock-out the associated compressor and flash a code on the ETC. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
(authority). Priority #1: BAS override. BAS network overrides zone humidity Priority #2: Network space humidity sensor, communicating thermostat or sensor Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
3 (HGRH) and energizes SOL 1, engaging cooling circuit no. 1 resulting in circuit no. 1 cooling mode operation. The unit is now in first stage cooling without HGRH. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
(Y2) temperature. This resets any pressure or freezestat lockouts. Smart Equipment™ economizer board details Figure 34: SE-ECO1001-1 economizer controller Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 114
24 V~ 24 VAC hot supplied for the outdoor air humidity sensor Connects through circuit trace to 24 V~ IN pin HOT Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 115
When wiring unit and other devices using the SA Bus and FC Bus, see Table "Cable for FC Buses and SA Buses in Order of Preference". Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
The ICB begins a call for heat when W1 is energized at the Unit Control Board (UCB). The ICB ignores W2 until ignition has been established. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
If the pressure switch is lost during an ignition trial W2 is energized. The control energizes the high gas period, the control immediately de-energizes spark output. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Rollout switch lockout shall not reset automatically. Following the pressure sensor check, the draft inducer is set to the pre-purge pressure setting. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
ICB keeps the main gas valve and control continues to monitor the gas valve circuit induced draft motor de-energized. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
10. Turn unit electrical power off. 11. If using a T-Stat, set the SE control to enable T- Stat. Operating instructions 1. Turn unit electrical power on. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Turn ON electric power to unit. units operating on 60 Hz power only. If thermostat set temperature is above room temperature, the main burners will ignite. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
1/2 cu. ft. 1 cu. ft. 2. Using the outlet pressure port on the gas valve, connect a manometer to monitor the manifold pressure. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 123
High 9. Once pressure has been checked, replace the cover screws covering the HI and LO pressure adjustment screws. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
National Fuel Gas Code, ANSI Z223.1/NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 125
Figure 37: 3 ton through 5 ton, 1/2 in. single stage gas valve Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
A red heating lead • A white, fan only lead Figure 38: 3 ton through 5 ton, 1/2 in. two stage gas valve Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 127
Figure 39: 6 ton through 12.5 ton 3/4 in. two stage gas valve Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
FAN ONLY (NO HEAT/COOL) FAST HEARTBEAT NO ALARMS IN MEMORY 2 PULSES 2 PULSES NORMAL IDLE SLOW HEARTBEAT FACTORY TEST MODE RAPID FLASH RAPID FLASH Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 129
Verify that there are no conditioned air leaks or heat exchanger breaches to interfere with ignition or the burners. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 130
None required - normal operation Normal operation with a steady on green LED None required - normal operation call for heating operation Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 131
If it is open, the switch must be reset before operation can resume. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Page 132
ICB. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...
Note: For more in-depth sequence of operation of the Smart Equipment™ control, refer to the Smart Equipment™ Controls Sequence of Operation Overview LIT-12011950. Installation Manual ZY Series 3 - 10 ton, ZXA7 6 ton 60 Hertz R-410A Johnson Controls Ducted Systems...