Replacing the burner insulating panel
Unscrew the ignition/detection electrode fixing screws and
remove it.
Remove the burner insulating panel (D) by inserting a blade
underneath the surface (as shown in the figure).
Remove any fixing glue residue.
Replace the insulating panel.
The new insulating panel does not need to be fixed in place
with glue as its geometry ensures perfect coupling with the
heat exchanger flange.
Reassemble the ignition/detection electrode using the
previously removed screws and replacing the relative seal.
B
Cleaning the siphon
Disconnect the tubes (A) and (B), remove the clip (C) and remove
the siphon.
Unscrew the bottom and the top caps, then remove the float.
Clean the parts of the siphon from any solid residues.
b
Do not remove the float and its sealing gasket as their pres-
ence is intended to prevent the escape of burnt gases into
the environment in the event of no condensation.
b
Once the operations have been completed, reassemble the
components by operating in the reverse order to what is de-
scribed, checking the floating seal and replace it if neces-
sary. If replacing the float gasket, make sure it is correctly
positioned in its seat (see figure in section).
b
At the end of the cleaning sequence, fill the siphon with wa-
ter (see "5.7 FIRST COMMISSIONING") before restarting
the boiler.
b
At the end of the siphon maintenance operations, it is
recommended to bring the boiler to condensing mode
for a few minutes and to check for leaks from the entire
condensate evacuation line.
A
B
C
34
D
C