11.5 EEX "ia" design for VT4A/ST4A and
VR4A/SR4A (fieldbus)
Important
The devices may only be operated in explosive areas if the
housing covers have been fully closed.
EC type-examination test certificate
TÜV 01 ATEX 1771
Designation
II 2G EEx ia IIC T4
II 2D T85 °C ... T med IP 67
The hazardous area design is based on the PTB's FISCO model
(FISCO = fieldbus intrinsically safe concept).
1
2
81
82
83
84
85
86
86
87
4
Fig. 57:
Connection diagram for PROFIBUS PA interface
connection
1
Flowmeter
2
Flowmeter sensor
Flowmeter sensor wire colors
Terminal
81
82
83
84
85
86
86
87
114
b) a)
E9
E9
42
2)
C9
C9
41
PA-
FF-
32
1)
PA+
FF+
31
4
VT4A/ST4A
3
b) a)
E9
E9
42
2)
C9
C9
41
PA-
FF-
32
1)
PA+
FF+
31
4
VR4A/SR4A
G00675
3
Transmitter
4
Functional ground
Wire color
Red
Blue
Pink
Gray
Yellow
Green
Brown
White
FV4000-VT4/VR4 / FS4000-ST4/SR4
A

11.5.1 PROFIBUS PA electrical connection

1) Terminals 31, 32
Function PA+, PA-
Connection for PROFIBUS PA to IEC 1158-2
U = 9 –32 V, I =
10 mA (normal operation)
13 mA (in the event of an error / FDE)
2) Terminals 41, 42
Function C9, E9
Switching output: Function can be selected via software as a pulse
output (fmax: 100 Hz, 1 ... 256 ms), min. / max. alarm or system
alarm.
Configured as NAMUR contact to DIN 19234.
Closed:
1 KΩ
Open:
> 10 KΩ
M12 plug-in connector
4
1
Fig. 58:
Assignment for connection using optional M12 plug-in
connector (view from the front looking at pin insert and
pins)
Pin
1
2
3
4
A
11.5.2 FOUNDATION Fieldbus electrical
connection
1) Terminals 31, 32
Function FF+, FF-
Connection for FOUNDATION Fieldbus (H1) to IEC 1158-2
U = 9 – 32 V, I =
10 mA (normal operation)
13 mA (in the event of an error / FDE)
2) Terminals 41, 42
Function C9, E9
Switching output: Function can be selected via software as a pulse
output (fmax: 100 Hz, 1 ... 256 ms), min. / max. alarm or system
alarm.
Configured as NAMUR contact to DIN 19234.
Closed:
1 KΩ
Open:
> 10 KΩ
Important
The installation instructions in accordance with EN 60079-14
must be complied with.
When commissioning the flowmeter, refer to EN 50281-1-2
regarding use in areas with combustible dust. After switching
off the supply power, wait t > 2 minutes before opening the
transmitter housing.
3
2
G00653
Assignment
PA+ (31)
NC
PA- (32)
Shield
D184B097U02