Charging Additional Refrigerant; Completely Recharging Refrigerant - Daikin EBVZ-D9W Installer's Reference Manual

Table of Contents

Advertisement

8
|
Piping installation

8.4.3 Charging additional refrigerant

To determine the additional refrigerant amount
Charging refrigerant: Setup
To charge additional refrigerant

8.4.4 Completely recharging refrigerant

To determine the complete recharge amount
Installer reference guide
88
If the total liquid piping
length is...
≤10 m
>10 m
INFORMATION
Piping length is the one-way length of liquid piping.
See
"8.3.3 Checking refrigerant piping:
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the gas stop valve
and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping⁠ – ⁠ 1 0 m)×0.050
R=Additional charge (kg) (rounded in units of
0.01 kg)
4
Setup" [
 84].
Then...
ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05