Unit installation

7.1.5 Installation patterns

Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Living room, kitchen, garage, attic, basement, storage
room
Technical room (i.e. room that is NEVER occupied by
persons)
b
a
Ventilation openings
Minimum floor area
Chimney
Release in case of
refrigerant leakage
Restrictions
Installer reference guide
56
Room type
PATTERN 1
A
b
1b
1a
N/A
Room A
Might be needed
Inside room A
See
"PATTERN
4
3" [
 60], and
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a
If no chimney is installed, this is the default point of release in case of
refrigerant leakage.
If needed, you can connect a chimney here.
b
Chimney
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
Actual release height:
release
1a 2a
For 180 l units => H
For 230 l units => H
1b 2b
For 180 l units => H
For 230 l units => H
PATTERN 2
A
B
b
c2
2b
2a
c1
Between room A
and B
Room A + Room B
Might be needed
Inside room A
4
1" [
 58],
"PATTERN
2" [
"Tables for PATTERN 1, 2 and
: Without chimney. From floor to top of the unit.
=1.66 m
release
=1.86 m
release
: With chimney. From floor to top of the chimney.
=1.66 m + Chimney height
release
=1.86 m + Chimney height
release
Allowed patterns
1, 2, 3
1, 2, 3, 4
PATTERN 3
A
b
3a
N/A
N/A
Connected to
outside
Outside
4
 58],
"PATTERN
4
3" [
 60]
PATTERN 4
A
c2
c1
Between room A
and outside
N/A
N/A
Inside room A
See
"PATTERN
4
4" [
 63]
ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05