18
|
Piping installation
18.4.3 To determine the additional refrigerant amount
Installer and user reference guide
98
A flow chart is available which gives an overview of the possibilities and actions to
be taken (see
"To charge refrigerant: Flow
INFORMATION
For final charge adjustment in the test laboratory, please contact your local dealer.
NOTICE
The refrigerant charge of the system must be less than 100 kg. This means that in
case the calculated total refrigerant charge is equal to or more than 95 kg you must
divide your multiple outdoor system into smaller independent systems, each
containing less than 95 kg refrigerant charge. For factory charge, refer to the unit
name plate.
Formula:
R=[(X
×Ø22.2)×0.37+(X
1
(X
×Ø12.7)×0.12+(X
×Ø9.5)×0.059+(X
4
5
R Additional refrigerant to be charged [in kg and rounded off to 1 decimal place]
X
Total length [m] of liquid piping size at Øa
1...6
A~C Parameters A~C (see tables below)
▪
Parameter A:
(b)
Piping length
≤30 m
>30 m
(a) In case of a multi-outdoor-unit system, add the sum of the individual outdoor unit
charge factors.
(b) Piping length is considered the distance from the outdoor unit to the farthest indoor
unit
CR Total indoor unit capacity connection ratio
▪
Parameter B:
RYYQ8~12
1.4 kg
(a) ONLY required for RYYQ8~20 models, NOT for RXYQ8~54 and RYYQ22~54.
▪
Parameter C:
chart" [
×Ø19.1)×0.26+(X
×Ø15.9)×0.18+
2
3
×Ø6.4)×0.022]+A+B+C
6
Parameter A
CR
50%≤CR≤105%
105%<CR≤130%
50%≤CR≤70%
70%<CR≤85%
85%<CR≤105%
105%<CR≤130%
Parameter B
RYYQ14
1.7 kg
4
101]).
(a)
A
8 HP
10~14 HP
0 kg
0.5 kg
0 kg
0.3 kg
0.5 kg
0.7 kg
1.0 kg
1.2 kg
1.5 kg
(a)
RYYQ16
RYYQ18 + RYYQ20
1.2 kg
RYYQ+RYMQ+RXYQ8~20U7Y1B
4P546228-1B – 2020.10
16~20 HP
0.5 kg
1.0 kg
0.5 kg
1.0 kg
1.5 kg
2.0 kg
2.0 kg
VRV IV+ heat pump