Daikin ERLA-DV17 Installer's Reference Manual page 74

Table of Contents

Advertisement

7
|
Unit installation
PATTERN 3
START PATTERN 3
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
3b
You CANNOT install the unit in the room. Place the unit in a larger
room.
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is
4.3 kg, use the row of 4.5 kg.
Charge (kg)
3.8
4
4.5
5
5.5
5.8
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value. Example: If the floor area is 22.50 m², use the
column of 20.00 m².
• For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is
4.3 kg, use the row of 4.5 kg.
• (*): The release height of the unit without chimney (for 180 l units: 1.66 m; for 230 l units: 1.86 m) is already
higher than the minimum required release height. => OK (no chimney needed).
Charge (kg)
3.8
4
4.5
5
5.5
5.8
Installer reference guide
74
Yes
No
1.66 (Unit=180 l)
16.04
17.77
22.49
27.76
33.59
37.36
5.00
10.00
3.30
2.10
3.47
2.21
3.91
2.49
4.34
2.77
4.78
3.04
5.04
3.21
3a
You can install the unit in room A if you lead the chimney outside
the building.
A
Minimum floor area (m²)
Release height without chimney (m)
Minimum release height (m)
Floor area (m²)
15.00
20.00
1.72
(*)
1.81
(*)
2.03
1.76
2.26
1.96
2.49
2.15
2.62
2.27
1.86 (Unit=230 l)
12.76
14.14
17.90
22.09
26.73
29.73
25.00
30.00
(*)
(*)
(*)
(*)
(*)
(*)
1.75
(*)
1.93
1.76
2.03
1.85
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
35.00
(*)
(*)
(*)
(*)
(*)
1.72