Daikin ERLA-DV17 Installer's Reference Manual page 300

Table of Contents

Advertisement

Field settings table
Breadcrumb Field code
Setting name
3.5
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
3.5
[0-02]
High ambient temp. for LWT add zone heating WD curve.
3.5
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
└─ Cooling WD curve
3.6
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
3.6
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
3.6
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
3.6
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
Additional zone
3.7
[2-0D]
Emitter type
└─ Setpoint range
3.8.1
[9-05]
Heating minimum
3.8.2
[9-06]
Heating maximum
3.8.3
[9-07]
Cooling minimum
3.8.4
[9-08]
Cooling maximum
Additional zone
3.A
[C-06]
Thermostat type
└─ Delta T
3.B.1
[1-0C]
Delta T heating
3.B.2
[1-0E]
Delta T cooling
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
Space heating OFF temp
4.3.2
[F-01]
Space cooling OFF temp
Space heating / cooling
4.4
[7-02]
Number of zones
4.5
[F-0D]
Pump operation mode
4.6
[E-02]
Unit type
4.7
[9-0D]
Pump speed limitation
Space heating / cooling
4.9
[F-00]
Pump outside range
4.A
[D-03]
Increase around 0°C
4.B
[9-04]
Overshoot
4.C
[2-06]
Room frost protection
Tank
5.2
[6-0A]
Comfort setpoint
5.3
[6-0B]
Eco setpoint
5.4
[6-0C]
Reheat setpoint
5.6
[6-0D]
Heat up mode
└─ Disinfection
5.7.1
[2-01]
Activation
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*
Range, step
Default value
R/W
[9-05]~[9-06], step: 1°C
[2-0D]=0:
40°C
[2-0D]=1:
45°C
[2-0D]=2:
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0D]=0:
18°C
[2-0D]=1:
5°C
[2-0D]=2:
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
15~37°C, step: 1°C
25°C
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
7°C
R/W
18~22°C, step: 1°C
22°C
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
[2-0D]≠2:
[2-0D]≠2 (Radiator):
R/W
3~10°C, step: 1°C
[2-0D]=2:
5°C
R/O
[2-0D]=2 (Radiator):
8°C
R/W
3~10°C, step: 1°C
5°C
R/W
14~35°C, step: 1°C
35°C
R/W
10~35°C, step: 1°C
20°C
R/W
0: Single zone
1: Dual zone
R/W
0: Continuous
1: Sample
2: Request
R/W (*5)
0: Reversible (*5)
R/O (*6)
1: Heating only (*6)
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6 80% pump speed during sampling
R/W
0: Restricted
1: Allowed
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
1~4°C, step: 1°C
2°C
R/W
0: Disabled
1: Enabled
R/W
30~[6-0E]°C, step: 1°C
55°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
0: No
1: Yes
3/13
Installer setting at variance with
default value
Date
Value