12/13
Field settings table
Breadcrumb Field code
Setting name
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
Is a DHW tank installed in the system?
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0A]
Tank volume
9.I
[E-0B]
Is a bizone kit installed?
9.I
[E-0C]
What bizone system type is installed?
9.I
[E-0D]
Is glycol present in the system?
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
9.I
[F-02]
--
9.I
[F-03]
--
9.I
[F-04]
--
9.I
[F-05]
--
9.I
[F-06]
--
9.I
[F-07]
--
9.I
[F-08]
--
9.I
[F-09]
Pump operation during flow abnormality.
9.I
[F-0A]
--
9.I
[F-0B]
Close shut-off valve during thermo OFF?
9.I
[F-0C]
Close shut-off valve during cooling?
9.I
[F-0D]
What is the pump operation mode?
9.I
[F-0E]
--
Bizone kit settings
9.P.1
[E-0B]
Bizone kit installed
9.P.2
[E-0C]
Bizone system type
9.P.3
[7-0A]
Add zone pump fixed PWM
9.P.4
[7-0B]
Main zone pump fixed PWM
9.P.5
[7-0C]
Mixing valve turning time
4P655201-1 - 2021.09
Range, step
Default value
R/O
0: No
1: Yes
R/W (*3)
0: No (*3)
R/O (*4)
1: Yes (*4)
R/O
0: No
1: Yes
R/W (*3)
0~8
R/O (*4)
0: EKHW, small volume
1: Integrated (*4)
3: EKHW, large volume
5: EKHWP
7: Third party tank, small coil
8: Third party tank, large coil
R/W
0: Disabled
1: Enabled
1
R/O (*4)
180 (*10)
230 (*11)
R/W
0: Not installed
1: -
2: Bizone kit installed
R/W
0: Without hydraulic separator / no
direct pump
1: With hydraulic separator / no direct
pump
2: With hydraulic separator / with direct
pump
R/O
0: No
1: Yes
0
R/W
0: Disabled
1: Enabled
R/W
10~35°C, step: 1°C
20°C
3~10°C, step: 1°C
3°C
2~5°C, step: 1°C
5°C
0
0
0
0
0
R/W
0: Disabled
1: Enabled
0
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0: Continuous
1: Sample
2: Request
R/W
20
R/W
0: Not installed
1: -
2: Bizone kit installed
R/W
0: Without hydraulic separator / no
direct pump
1: With hydraulic separator / no direct
pump
2: With hydraulic separator / with direct
pump
R/W
20~95%, step 5%
95%
R/W
20~95%, step 5%
95%
R/W
20~300 sec, step 5 sec
125 sec
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
Installer setting at variance with
default value
Date
Value
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*