6
|
Application guidelines

6.6.3 Power limitation process

Installer reference guide
60
A Outdoor unit
B Indoor unit
C Energy management system
a Power limitation activation (4 digital inputs)
b Backup heater
P
i
a
DI1
DI3
DI4
P
Power input
i
t Time
DI Digital inputs (power limitation levels)
a Power limitation active
b Actual power input
Setup
Demand PCB (option EKRP1AHTA) needed.
Maximum four digital inputs are used to activate the corresponding power
limitation level:
-
DI1 = strongest limitation (lowest energy consumption)
-
DI4 = weakest limitation (highest energy consumption)
Specification of the digital inputs:
-
DI1: S9S (limit 1)
-
DI2: S8S (limit 2)
-
DI3: S7S (limit 3)
-
DI4: S6S (limit 4)
Refer to the wiring diagram for more information.
Configuration
Set the power consumption control settings in [9.9] via the user interface (for the
description of all settings, see
-
Select limitation by digital inputs.
-
Select the type of limitation (power in kW or current in A).
-
Set the desired power limitation level corresponding to each digital input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority
is fixed: DI4 priority>...>DI1.
The outdoor unit has better efficiency than the electrical heater. Therefore, the
electrical heater is limited and turned OFF first. The system limits power
consumption in the following order:
1
Turns OFF the backup heater.
2
Limits the outdoor unit.
3
Turns OFF the outdoor unit.
b
t
"Power consumption
4
control" [
 227]):
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05