5.2.2 Protective devices

The tasks described in this section may only
be carried out by a qualified electrician.
The following conditions must be met when in-
stalling the protective devices in the upstream elec-
trical installation:
Residual current device
n National regulations must be observed
(e.g. IEC 60364‑7‑722 (in Germany DIN
VDE 0100‑722)).
n A differential current sensor for DC resid-
ual current monitoring > 6 mA in accord-
ance with IEC 62752 is integrated in the
product.
n „The product must be protected by a re-
sidual current circuit breaker. As a min-
imum, a type A residual current circuit
breaker must be used.
n No other circuits may be connected to
the residual current circuit breaker.
12
Supply line fuse (e.g. miniature circuit breaker,
NH fuse)
n National regulations must be observed
(e.g. IEC 60364‑7‑722 (in Germany DIN
VDE 0100‑722)).
n The fuse for the supply line must be de-
signed for the product, taking account,
among other considerations, of the rating
plate, the required charging power and
the supply line (line length, cable cross-
section, number of outer conductors, se-
lectivity).
n The rated current of the fuse for the sup-
ply line must not exceed 40 A (with C
characteristics).
Shunt release
u Check whether a shunt release is legally pre-
scribed in the country of use.
1 "2.2 Intended use" [} 3]
n The shunt release must be positioned
next to the line circuit breaker.
n The shunt release and the line circuit
breaker must be compatible with each
other.
5.3

Transporting the product

ATTENTION
Material damage due to improper transportation
Collisions and impacts may damage the product.
u Avoid collisions and impacts.
u Transport the product to the place of installa-
tion in the packed condition.
u Set the product down on a soft base.
5.4

Opening the product

The tasks described in this section may only
be carried out by a qualified electrician.