INSTALLATION (SITE, TYPE OF SUPPORT, NECESSARY FREE SPACE)

– Install the HP outdoors at more than 3.5 meters from the pool, as per applicable laws (in France NF C 15 100).
– Place the HP on a surface that is stable, solid (able to bear the weight of the device) and level (prepare a concrete base if necessary, see below
dimensions adviced).
- Maintain 1 m (30 cm minimum) of open space in front of the vertical air intake grids (3 side of the HP), 1m at the back is recommended to facilitate
the access to the visit hatch and 3 m at the outlet of the fan (on the top) of open space without any obstacles.
– Prepare sufficient space around the HP for maintenance operations.
– Prepare a water evacuation system close to the HP to protect the installation zone.
– Keep the HP out of the reach of children, insofar as possible.
- The side where the display is installed can be reversed (see p12).
The HP should never be installed:
– In an area covered by sprinkling systems, or subject to spray or running water or mud (close to a road, take into account the effects of wind),
– Under a tree,
– Close to a source of heat or of flammable gas,
– In an area where it would be exposed to oil, flammable gases, corrosive products, and compounds containing sulphur,
– Close to equipment operating at high frequencies,
– In a place where snow is likely to accumulate,
– In a place where it could be flooded by the condensates produced by the device as it operates,
– On a surface that could transfer the vibrations to the house.
Advice: dampen the possible noise nuisance caused by your HP:
– Do not install it close to or underneath a window.
– Install it in an open area (sound waves bounce off surfaces).
– Install a sound barrier around the HP, making sure to maintain the required distances.
– Install 50 cm of PVC piping at the water inlet and outlet of the HP.
To improve its performance, it is recommended to insulate the piping between the HP and the swimming pool, especially if the distance is signi-
ficant.
Room to maintain around the HP:
Minimum dimensions of the concrete slab
The HP must be installed on a fixed and solid basis. Use the adjustable feet to level the HP.