Pentair ULTRATEMP Installation And User Manual

Pentair ULTRATEMP Installation And User Manual

Hide thumbs Also See for ULTRATEMP:
Table of Contents

Advertisement

ULTRATEMP
®
HEAT PUMP
INSTALLATION AND
USER'S GUIDE
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ULTRATEMP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pentair ULTRATEMP

  • Page 1 ULTRATEMP ® HEAT PUMP INSTALLATION AND USER'S GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS...
  • Page 2: Table Of Contents

    CUSTOMER SERVICE / TECHNICAL SUPPORT If you have questions about ordering Pentair Aquatic Systems (“Pentair”) replacement parts, and pool products, please use the following contact information: Customer Service (8 A.M. to 4:30 P.M. — Eastern Technical Support and Pacific Times) Sanford, North Carolina (8 A.M.
  • Page 3: Important Warning And Safety Instructions

    Persons taking medication which induce drowsiness, such as tranquilizers, antihistamines or anticoagulants should not use spas UltraTemp heat pumps are listed by ETL as complying with the latest edition or hot tubs. of the “UL Standard for Safety for Heating and Cooling Equipment”, UL 1995 and CSA C22.2 No.
  • Page 4 ULTRATEMP MENU TREE QUICK START GUIDE ® 1. Push the on/off button to turn the unit on, the green “on” light should be lit. 2. Select either Pool or Spa mode. The default is pool mode. 3. Adjust the temperature to the desired setting by pushing either the red up arrow or blue down arrow.
  • Page 5: Before Installing The Heat Pump

    General Features ® • Dual digital thermostats offer precise temperature Your Pentair heat pump will provide you with years of control to maintain the desired separate water heated pool enjoyment. Heat pumps operate by taking temperatures in pool/spa combinations without heat from the surrounding air and transferring it into the overheating or wasting energy.
  • Page 6: Installation And Location

    When pool equipment is located below the pool surface, a leak from any component can cause large scale water loss or flooding. Pentair Water Pool and Spa, Inc. cannot be responsible for such water loss or flooding which may cause damage to the product.
  • Page 7: Location And Clearances

    (Manufacturer’s proximity to public access areas. recommendation). The UltraTemp Heat Pump must be placed to provide 3. Install a minimum of five (5) feet [1.52 m] from the ®...
  • Page 8: Water Connections And Plumbing

    Note: Be advised that when pool equipment is located below the pool surface a leak can result in large-scale COIL water loss or flooding. Pentair is not responsible for such water loss or flooding or damage. 1-3/8" HEX BOLT (installer provided)
  • Page 9: Water Pressure Switch Adjustment

    If this happens, is plumbed to the inlet, located on the right side of the install a directional fitting or elbow where the return UltraTemp Heat Pump. Heated water flows through the ®...
  • Page 10: Water Pressure Switch Adjustment

    The pressure switch in a counterclockwise direction Pentair heat pump may be used in conjunction with a until the “LOW WATER FLOW” Alarm and Red gas or electric heater or any combination of heat sources Service LED vanish, time delay countdown will including solar.
  • Page 11 Flow Meter Flow Meter balancing 3" Ball Valve Bypass Minimum To Pool To Pool Pool Pump Minimum Pool Pump 3" PVC Pipe Minimum 3" PVC Pipe Four Heat Pump Plumbing Layout ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 12: Electrical Connections And Wiring

    Association (NFPA) 70 in the United States, and in pages 9-11. Canada, the Canadian Electrical Code (CEC) C22.1, The UltraTemp ® Heat Pump must include a definite unless local code requirements indicate otherwise.
  • Page 13: Wiring Diagram - (Single Phase - 50/60 Hz)

    /RED /RED PURPLE Compressor AutoSet Contactor Contactor BROWN PINK See Users Guide BLACK ORANGE for instructions on connecting to filter pump Incoming 230 VAC Power Connection GREEN Label P/N 473073 Rev. D ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 14: Wiring Diagram - (Three Phase - 60Hz)

    Inco mi ng 230 VAC 60 Hz Power Connection GREEN GREEN 3 Phase Power Connection Label P/N 473073 Rev. D Note: If red LED is on, swap any two phases. Label P/N 474022 Rev. B ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 15: Wiring Diagram - (Three Phase - 50Hz)

    BLUE/WHITE BLACK ORANGE ORANGE/WHITE ORANGE/WHITE YELLOW (L1) Incoming 380 VAC 50 Hz GREEN 3 Phase Power Connection Label P/N 474017 Rev. B Note: If red LED is on, swap any two phases. ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 16: Connecting To An Automation System

    CONNECTING TO AN AUTOMATION SYSTEM Remote Operation 4. Run the wires from the pool/spa remote control The UltraTemp Heat Pump be connected to an ® system into the upper electrical compartment. automation system via the remote spade terminals on the back of the control board or via the RS-485 5.
  • Page 17 Center via the Heat Pump Spade Terminals To connect the UltraTemp Heat Pump cable to the 6. Insert the UltraTemp cable plug onto the gas heater ® Personality Board in the IntelliTouch or EasyTouch Load terminal connector, located on the left side of the Center: Personality Board.
  • Page 18 EasyTouch ® load center before servicing. 1. Unlatch the IntelliTouch or EasyTouch load center The UltraTemp Heat Pump can be controlled by an ® front door spring latches, and open the front door. IntelliTouch or EasyTouch system via the RS-485 2.
  • Page 19: Pin Configuration For Heat Pump Control

    Connecting the IntelliTouch or EasyTouch to Heat Pump 6. Rotate the bezel back upwards into position and 1. Turn off the power to both the remote pool/spa control system and the UltraTemp Heat Pump. reinstall the 4 retaining screws. ®...
  • Page 20: Operating The Heat Pump

    S E T = 78 ACT = 78 cabanas, or fencing. 6. Pentair recommends the use of a pool cover. Besides providing a valuable safety feature, a pool cover will reduce heat loss, conserve chemicals, and reduce PRESS ON/OFF TO START...
  • Page 21: Operator Setup Menu Tree Guide

    OUTPUT STATUS displayed when the FAN - FAN associated input/output is COMP - COMPRESSOR ON and zero (0) is displayed PMP - FILTER PUMP when input/output is OFF. REV - REVERSING VALVE ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 22: Set Water Temperature Offset

    Temperature Scale - C˚ or F˚ Defrost Cycle The control board can display temperatures in either The UltraTemp Heat Pump may enter a defrost cycle ® degrees Fahrenheit or Celsius. The temperature scale if air temperatures are around 50° F (10° C).
  • Page 23: Control Panel Menu Tree Guide

    Menu appears only if Autoset is enabled at the factory. and Spa by using the UP and DOWN arrows. Menu appears only if a delay is active. Menu appears only if defrost is enabled in the operator menu. **** ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 24: Stopping And Starting The Heat Pump

    Heat Pump Timer Starting and Stopping the Heat Pump This feature is an adjustable timer to allow the heat pump The UltraTemp Heat Pump is started and stopped with ® to run (Green LED ON) and then turn OFF (Green LED the ON/OFF button.
  • Page 25: Serial Remote

    In serial remote operation, the heat pump is made to the ON and OFF options. start and stop via a serial RS-485 communications link with a Pentair automation controller. This means the Set the interval (1-4 hours) from the control panel to remote automation controls override the heat pump’s control when the heat pump send a signal to check the local set point.
  • Page 26: Timers And Delays

    1. Water Sensing Timer HIGH WATER Water temperature is above 108°. One minute timer to allow water from the pool to TEMP reach the UltraTemp Heat Pump before acquiring ® temperature. This timer initiates when water first LOW WATER begins to run from stopped or low water flow Water temperature is below 40°.
  • Page 27: Maintenance

    Owner Inspection Copper 0 ppm Pentair recommends that you inspect your heat pump on * Concentration levels taken from “Basic Pool and Spa Technology” a continual basis and especially after abnormal weather published by NSPI (National Spa and Pool Institute).
  • Page 28: Professional Maintenance And Service

    Owner Inspection, Continued Professional Maintenance and Service The UltraTemp Heat Pump will produce condensation ® The maximum heat output and efficiency of a heat pump (water) while in operation. The heat pump base is is dependent upon the quality and performance of the designed to allow the condensation to exit through major components used.
  • Page 29: Technical Information

    TECHNICAL INFORMATION Electrical Supply - Voltage Requirements UltraTemp ® Modelos 120 H/C 140 H/C 120C 140C 100I Voltage/Phase/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/3/60 208-230/1/60 208-230/3/60 208-230/3/60 230/1/50 380-400/3/50 Min. Circuit Ampacity (Amp) Recommended Fuse Size Max Fuse Breaker Size...
  • Page 30: Heat Pump Pressure Drop

    HP1200R UltraTemp 70 UltraTemp 70 UltraTemp 90 UltraTemp 90 UltraTemp 110 UltraTemp 110 UltraTemp 120 UltraTemp 120 UltraTemp 120 H/C UltraTemp 120 H/C UltraTemp 140 UltraTemp 140 UltraTemp 140 H/C UltraTemp 140 H/C UltraTemp 120C UltraTemp 120C UltraTemp 140C UltraTemp 140C...
  • Page 31: Troubleshooting

    Should have 120 volts to ground and 240 volts across power Troubleshoot Electrical Box. legs. A boost transformer may be needed closer to the heat pump to get voltages within proper range. Refer to 10K Ohm Temperature Resistance Chart on page 25. ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 32 5 alarms of any kind within one hour. reset in one hour or can be manually reset by again. This alarm most likely caused the five alarms in one pressing the ON/OFF button. hour. ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 33 Call your dealer for advice. Call the factory for advice. Pool is not covered. High wind speed over pool. Shaded pool area.” ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 34 Contactor. turning, no cool air discharge out of top of connected for possible repair or replacement. heater. Unit ON, and Set Temperature is above Actual, but Unit is not heating. ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 35: Replacement Parts

    REPLACEMENT PARTS Illustrated Parts View DETAIL B – Single Phase DETAIL B DETAIL B – Three Phase ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 36: Parts List

    Auto Set Board Bezel LBL Kit [Not Shown] 474237 Clip Retension Comp. Pwr. [Not Shown] 474270Z Leak Repair Kit [Not Shown] 474321 3 IN Receiver [Not Shown] 473054Z Coil Guard [Not Shown] ULTRATEMP Heat Pump Installation and User’s Guide ®...
  • Page 37: P/N 474099 Rev. H 1/23/14

    United States and/ or other countries. Unless expressly noted, names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Pool and Spa, Inc. Those names and brands may be the trademarks or registered trademarks of those third parties.