F&F LE-03MW CT User Manual

F&F LE-03MW CT User Manual

Electricity consumption meter 3-phase, 2-way tariff
Hide thumbs Also See for LE-03MW CT:

Advertisement

Quick Links

F&F Filipowski sp.j.
ul. Konstantynowska 79/81
95-200 Pabianice
Phone/Fax (42) 215 23 83, 227 09 71
e-mail: biuro@fif.com.pl
www.fif.com.pl
LE-03MW CT
Electricity consumption meter
3-phase, 2-way
tariff
User manual
v. 1.3 (201015)
www.fif.com.pl

Advertisement

Table of Contents
loading

Summary of Contents for F&F LE-03MW CT

  • Page 1 F&F Filipowski sp.j. ul. Konstantynowska 79/81 95-200 Pabianice Phone/Fax (42) 215 23 83, 227 09 71 e-mail: biuro@fif.com.pl www.fif.com.pl LE-03MW CT Electricity consumption meter 3-phase, 2-way tariff User manual v. 1.3 (201015) www.fif.com.pl...
  • Page 2: Table Of Contents

    LE-03MW CT – user manual Table of contents TABLE OF CONTENTS ........................... 2 1. PURPOSE ..............................3 2. DEVICE CHARACTERISTICS ........................3 3. MEASURED VALUES ..........................4 4. OPERATOR PANEL ............................ 4 5. TECHNICAL SPECIFICATIONS ........................9 6. COMPLIANCE AND MARKING ........................ 10 7.
  • Page 3: Purpose

    LE-03MW CT – user manual 1. Purpose LE-03MW CT is an electronic, 2-way three-phase electricity meter, designed for measurement in a semi-indirect system. A built-in real-time clock allows energy consumption to be measured by different tariff zones. RS-485 with Modbus RTU protocol and optical port compliant with EN62056 (IEC1107) provide remote reading and configuration of the meter.
  • Page 4: Measured Values

    LE-03MW CT – user manual 3. Measured values  Active energy consumed and exported  Inductive and capacitive reactive energy  Phase voltages  Phase currents  Active power (absolute value)  Reactive power (absolute value)  Apparent power  Power factor (absolute value) ...
  • Page 5 LE-03MW CT – user manual 4.1. Description of the display elements Current tariff indicator. Symbol – indicates which parameter group the value displayed in the numeric field is associated with. It may be a tariff (T1, T2, T3 T4) or phase (L1, L2, L3) indicator.
  • Page 6 LE-03MW CT – user manual 4.3. Data displayed on the LCD Page Parameter Unit Symbol Format Date XX-XX-XX Time XX-XX-XX Total active energy consumption 6+2 000000.00 T1 tariff – active energy consumption 6+2 000000.00 T2 tariff – active energy consumption 6+2 000000.00...
  • Page 7 LE-03MW CT – user manual Page Parameter Unit Symbol Format Frequency 2+2 00.00 T1 tariff – power demand 6+2 000000.00 T2 tariff – power demand 6+2 000000.00 T3 tariff – power demand 6+2 000000.00 T4 tariff – power demand 6+2 000000.00...
  • Page 8 LE-03MW CT – user manual CodE 09 – total energy = energy consumed – energy exported Meter IR address 12345678 MODBUS address Id 255 1200, 2400, Baud rate bd 9600 4800, 9600 Software version V 1.01...
  • Page 9: Technical Specifications

    LE-03MW CT – user manual 5. Technical Specifications reference voltage 3×230/400 V minimum current / base current 0.25 / 1.5 A maximum current minimum detection current 0.003 A measured voltage 100÷289 V AC L- L 173÷500 V AC rated frequency...
  • Page 10: Compliance And Marking

    LE-03MW CT – user manual reading indication 2×LED operating temperature -25÷55°C terminal 2.5 mm screw terminals 76×100×65 mm dimensions (4.5 of the DIN module) installation on TH-35 mm rail ingress protection IP51 Insulation protection class Class II housing self-extinguishing plastic UI94 V-0 6.
  • Page 11: Dimensions

    LE-03MW CT – user manual 7. Dimensions 8. Connection...
  • Page 12: Communication Protocol

    LE-03MW CT – user manual 9. Communication protocol The meter is equipped with an RS-485 interface that supports the Modbus RTU communication protocol. Default communication parameters: Modbus address communication rate 9600 bps The current communication parameters (Modbus address, baud rate) can be read from the views on the LCD display.
  • Page 13 LE-03MW CT – user manual Register Feature Type R/W Quantity Settings Serial number Meter Modbus address U16 R/W 1÷247 Baud rate U16 R/W 1200, 2400, 4800, 9600 Software version Float Hardware version Float Current transformer CT U16 R/W List of setting codes in...
  • Page 14 LE-03MW CT – user manual L2 phase – reactive power Float L3 phase – reactive power Float Total apparent power Float...
  • Page 15 LE-03MW CT – user manual Register Feature Type R/W Quantity Settings L1 phase – apparent power Float L2 phase – apparent power Float L3 phase – apparent power Float Total power factor Float L1 phase – power factor Float L2 phase – power factor Float L3 phase –...
  • Page 16 LE-03MW CT – user manual Register Feature Type R/W Quantity Settings 12 A L1 phase – exported reactive Float energy 12C L2 phase – exported reactive Float energy 12E L3 phase – exported reactive Float energy Value dependent on the set calculation 130 T1 tariff –...
  • Page 17 LE-03MW CT – user manual (see register 11) 14 A T3 tariff – consumed active energy Float 14C T3 tariff – exported active energy Float Value dependent on the calculation 14E T3 tariff – total reactive energy Float option set (see register 11) 150 T3 tariff –...
  • Page 18 LE-03MW CT – user manual 9.2 Current transformer The current transformer ratio of the meter can be set remotely via the Modbus RTU interface or locally using the PROG button. To set it manually: 1) switch off and on the power supply of the meter;...
  • Page 19 (*) Transformer ratios 30/5, 80/5, 750/5 can only be set via the Modbus RTU interface. Warning! For advanced configuration of the LE-03MW CT meter (tariff zones, holidays, etc.) we recommend the free configuration software LE Config. Program available for download from the www.fif.com.pl website.
  • Page 20: Manufacturer Warranty

    LE-03MW CT – user manual 10. Manufacturer warranty 1. The meter is covered by a 24-month warranty from the date of purchase. 2. The warranty valid only with proof of purchase. 3. A warranty claim should be submitted at the point of purchase or directly to the manufacturer: (phone (42) 22709 71;...

Table of Contents