F&F LE-03MW User Manual

F&F LE-03MW User Manual

Electricity consumption meter 3-phase, bi-directional, tariff-based
Hide thumbs Also See for LE-03MW:

Advertisement

Quick Links

LE-03MW
Electricity consumption meter
3-phase, bi-directional,
tariff-based
User manual
v. 1.0 (180409)
www.fif.com.pl

Advertisement

Table of Contents
loading

Summary of Contents for F&F LE-03MW

  • Page 1 LE-03MW Electricity consumption meter 3-phase, bi-directional, tariff-based User manual v. 1.0 (180409) www.fif.com.pl...
  • Page 2: Table Of Contents

    LE-03MW – user manual Table of contents 1. PURPOSE ............................... 3 DEVICE CHARACTERISTICS ........................3 MEASURED VALUES ..........................4 OPERATOR PANEL ..........................4 TECHNICAL SPECIFICATIONS ......................... 9 COMPLIANCE AND MARKING ......................10 7. DIMENSIONS ............................11 8. CONNECTION ............................11 COMMUNICATION PROTOCOL ......................
  • Page 3: Purpose

    LE-03MW – user manual 1. Purpose LE-03MW is an electronic bi-directional three-phase electricity meter, compliant with the MID Directive, designed for direct measurement. The built-in real-time clock allows the measurement of energy consumption divided into different tariff zones. Communication interfaces:...
  • Page 4: Measured Values

    LE-03MW – user manual 3. Measured values  Active energy consumed and exported;  Inductive and capacitive reactive energy;  Phase voltages;  Phase currents;  Active power (absolute value);  Reactive power (absolute value);  Apparent power;  Power factor (absolute value);...
  • Page 5 LE-03MW – user manual 4.1. Description of the display elements Current tariff indicator Symbol - indicates to which group of parameters the value displayed in the numeric field is related. It may be a tariff (T1, T2, T3 T4) or phase (L1, L2, L3) indicator.
  • Page 6 LE-03MW – user manual 4.3. Data displayed on the LCD Page Parameter Unit Symbol Format Date XX-XX-XX Time XX-XX-XX Total active energy consumption 6+2 000000.00 Tariff T1 - active energy 6+2 000000.00 consumption Tariff T2 - active energy 6+2 000000.00...
  • Page 7 LE-03MW – user manual Page Parameter Unit Symbol Format Frequency 2+2 00.00 Tariff T1 - power demand 6+2 000000.00 Tariff T2 - power demand 6+2 000000.00 Tariff T3 - power demand 6+2 000000.00 Tariff T4 - power demand 6+2 000000.00...
  • Page 8 LE-03MW – user manual Pulse output 1, 10, 100, 1000 S0 1000 CodE 01 - total energy = energy consumed, CodE 05 - total energy = energy Measuring mode of total energy consumed + energy CodE 01 consumption exported CodE 09 - total...
  • Page 9: Technical Specifications

    LE-03MW – user manual 5. Technical Specifications reference voltage 3×230/400 V minimum current/base current 0.25/5 A maximum current 80 A minimum detection current 0.04 A measured voltage 100÷289 V AC 173÷500 V AC Rated frequency 50 Hz accuracy of measurement...
  • Page 10: Compliance And Marking

    LE-03MW – user manual 6. Compliance and marking Directive 2004/22 /EC. Certificate number: SGS 0120/SGS0306. The meter is marked with an individual serial number, which makes it possible to identify it unambiguously. The marking is indelible (laser engraving). The meter has the option of sealing the input and output terminals, preventing the meter from being bypassed.
  • Page 11: Dimensions

    LE-03MW – user manual 7. Dimensions 8. Connection...
  • Page 12: Communication Protocol

    LE-03MW – user manual 9. Communication protocol The meter is equipped with an RS-485 interface that supports the Modbus RTU communication protocol. Default communication parameters: Modbus address communication rate 9600 bps The current communication parameters (Modbus address, baud rate) can be read from the LCD display.
  • Page 13 LE-03MW – user manual Register Function R/W Qua Settings ntity Serial number Modbus address of the meter U16 R/W 1÷247 Transmission rate U16 R/W 1200, 2400, 4800, 9600 Software version Float Hardware version Float Configuration of the pulse output Float R/W...
  • Page 14 LE-03MW – user manual Register Function Type R/W Qua Settings ntity L1 phase - apparent power Float L2 phase - apparent power Float L3 phase - apparent power Float Total power factor Float L1 phase - power factor Float L2 phase - power factor...
  • Page 15 LE-03MW – user manual Register Function R/W Qua Settings ntity 12A L1 phase - exported reactive energy Float 12C L2 phase - exported reactive energy Float L3 phase - exported reactive energy Float T1 tariff - total active energy Float...
  • Page 16: Manufacturer's Warranty

    LE-03MW – user manual Warning! For advanced configuration of the LE-03MW meter (tariff zones, holidays, etc.) we recommend the free configuration software LE Config Program available for download from the www.fif.com.pl website. 10. MANUFACTURER'S WARRANTY Warning! Do not make any changes to the unit yourself. Doing so can result in damage to or improper operation of the device, which in turn can lead to damage to the controlled device and pose a threat to people operating it.