Danfoss iC7 Series Installation Manual page 10

In-bottom/out-top cooling kit for fa09-fa10, frequency converters
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

In-bottom/Out-top Cooling Kit for FA09-FA10
Installation Guide
1051 (41.4)
2x Ø 8 (0.3)
Drive Mounting Holes
Illustration 8: FA10 Mounting Plate Template
2.6 Assembling the Ducts
The top and bottom ducts are telescopic ducts that collapse to simplify installation. To assemble the ducts before installation, use
the following steps. Refer to
Procedure
1.
Cut the strip of ribbed EPDM rubber seal into 4 pieces. Use the following measurements:
a.
For FA09 frequency converters, cut 2 strips of 581 mm (22.9 in) for the top duct, and 2 strips of 682 mm (26.9 in) for
the bottom duct.
b.
For FA10 frequency converters, cut 2 strips of 849 mm (33.4 in) for the top duct, and 2 strips of 877 mm (34.5 in) for
the bottom duct.
2.
Peel the paper off the self-adhesive seals. Place 1 strip on the outside bottom edge of the inner sleeve of each duct, and 1
strip on the upper inside edge of the outer sleeve of each duct.
10 | Danfoss A/S © 2022.03
280 (11.0)
271 (10.7)
Illustration
9.
2x Ø 8 (0.3)
Drive Mounting Holes
AN371942791357en-000101 / 136R0254
Installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

176f4038176f4039

Table of Contents