Input and Output Module IO101

3.4.2
3.4.2.1

Description

The terminals for the following are located on the input and output module IO101:
4 current transformers (3 transformers always as protection-class current transformers, the 4th optionally
as protection-class or instrument transformer)
8 binary inputs
6 binary outputs, of which:
4 standard make contacts (type S)
2 standard change-over contacts (type S)
The connections are distributed over:
1 x 8-pole current terminal
2 x 14-pole voltage terminal
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-M, Edition 12.2021
3.4 Input and Output Modules of Non-Modular Devices (7xx81, 7xx82)
Function Description
Input and output module
4 current measuring inputs, 8 binary inputs, 6 binary outputs
Input and output module
4 current measuring inputs, 4 voltage measuring inputs, 8 binary inputs,
6 binary outputs
Input and output module
8 current measuring inputs, 4 binary inputs, 4 binary outputs
Input and output module
12 binary inputs, 7 binary outputs
Input module
12 temperature inputs
Input and output module
5 binary inputs, 2 binary outputs
Input and output module
7 binary inputs, 5 binary outputs