Selectivity Implemented By Combinations Of Protective Devices; Molded Case Circuit Breakers And Downstream Fuse - Siemens SENTRON Configuration Manual

Protective devices selectivity for 3va molded case circuit breakers
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Selectivity implemented by combinations of
protective devices
4.1

Molded case circuit breakers and downstream fuse

Note
Tolerance ranges for fuses
If the selectivity properties of a protective device combination comprising circuit breaker and
fuse, it is clear that a permissible tolerance range of ±10 % must be applied to the current-
time tripping characteristics of the circuit breakers.
The tolerance range is reduced to ±6 % if Siemens type 3NA LV HRC fuses are used.
Circuit breakers with LI or LSI releases behave selectively in the overload zone with respect
to a downstream fuse if a safety margin t
the tolerance band of the time-current characteristics and the lower tripping characteristic of
the L release.
The times specified are empirical values and also take into account the data for the products
of other manufacturers.
Circuit breaker without an S release
Selectivity for 3VA molded case circuit breakers
Configuration Manual, 08/2016, A5E03603181010-01
Dynamic selectivity zone
Tripping characteristic
Time-current characteristic
of around 1 s is provided between the top edge of
A
4
47