Interface Modules - Siemens SIPROTEC 4 7VE61 Manual

Multifunction paralleling
Table of Contents

Advertisement

Pickup voltages of the BI6
Table 3-12
Binary Inputs
BI6
Factory settings for devices with rated power supply voltages of DC 24 V to 125 V
1)
2)
Factory settings for devices with rated power supply voltages of DC 110 to 220 V and AC 115 V to 230 V
3)
Use only with control voltages 220 V or 250 V
Jumpers X71, X72 and X73 on the C–I/O-8 board serve to set the bus address. The jumpers must not be
changed. The following table lists the jumper presettings.
Bus address
Table 3-13
Jumper
X71
X72
X73
3.1.2.4

Interface Modules

Austausch von Schnittstellenmodulen
The interface modules are located on the C–CPU-2 board ((1) in
figure shows the PCB with location of the modules.
Figure 3-2
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Jumper setting for the Pickup voltages (DC voltage) of the binary inputs BI6 on the C–I/O-8
board
Jumper
X21
Jumper settings of the Bus address on the input/output board C-I/O-8
Housing size
1
/
3
2–3 (L)
2–3 (L)
1–2 (H)
19 V Threshold
1)
88 V Threshold
1–2
2–3
Housing size
2–3 (L)
2–3 (L)
1–2 (H)
Figure 3-2
Mounting and Commissioning
3.1 Mounting and Connections
3)
176 V Threshold
3–4
1
/
2
and
Figure
3-3). The following
3)
155