Rheem 864 Series Owner's Manual And Installation Instructions page 63

Continuous flow gas indoor water heater
Table of Contents

Advertisement

Condensate Trap and Condensate Drain Line
Where the installation requires a Condensate Trap and condensate drain line:
Remove the clamp and rubber cap from the condensate drain spigot on the water heater flue outlet
1.
assembly.
2.
Locate the Condensate Trap in a suitable position adjacent to
the water heater.
The loop of the condensate trap MUST BE below the spigot
of the condensate drain section to ensure proper drainage.
Secure to the wall with the pipe saddle supplied.
If required, trim the hose length to suit the installation. Ensure
the structure of the Condensate Trap including the fixed loop
is not altered and the trimmed hose seals to the spigot.
Fill the condensate trap with water.
3.
Fit the shorter end of the silicone tube to the 16 mm spigot of
4.
the water heater flue outlet, ensuring a constant fall to the
condensate trap.
Secure to the spigot with the clamp removed in step 1.
Ensure the silicon hose is not kinked.
Plumb the outlet of the Condensate Trap to drain.
5.
Ensure the silicon hose is not kinked.
The drain line should be as short as possible, have a continuous fall all the way from the Condensate Trap
to the discharge outlet and have no tap, valves or other restrictions in the pipe work.
The outlet of the drain line must be in such a position that flow can be easily seen, but arranged so the
condensate will not cause injury, damage or nuisance.
Warning: Failure to fill with water may cause flue gasses to escape through the condensate trap. Check
regularly to ensure the condensate trap is filled with water, replenishing when required.
Notes
AS/NZS 3500.4 section 5.12, is used as a guide in preparing the following drainage recommendations.
As the condensate is mildly acidic, copper tube and fittings must not be used as they will corrode.
Use UPVC (Unplasticised Polyvinyl Chloride) or PE (polyethylene) piping.
The outlet of the drain line must be in such a position that flow can be easily seen, but arranged so that
discharge will not cause injury, damage or nuisance.
The drain line must not discharge onto electrical connections, earth stakes, copper pipe, concrete paths
or into a pond.
For a multiple unit installation, refer to
Installation"
on page 74.
"Multiple Water Heater Condensate Trap and Condensate Drain Line
63
Condensate Trap and Condensate Drain Line
FLUEING

Advertisement

Table of Contents
loading

Table of Contents