0
Encoding LE 513
Following functions can be encoded on the plug-in board using the DIP-switch.
DIP-switch 1 on ON =
In the case of a group fault (e.g. with broken motor line or missing end module) the control panel will be
switched to alarm i.e. the smoke vent opens.
DIP-switch 2 on ON =
In the case of a line fault (e.g. with interrupted button line or missing terminal resistor) the control panel will be
switched to alarm, i.e. the smoke vent opens.
DIP-switch 3 on ON =
Smoke detector alarm cannot be reset pressing the button in the smoke vent button once. DIP-switch 3 must be
switched to OFF if you want to carry out a remote reset of smoke detectors via the smoke vent button. Should only be
used if DIP-switch 4 and 5 = OFF.
DIP-
switch
4 on ON =
Groups and lines connected in series will be released in the case of an alarm.
Important:
switched OFF/ON for "Smoke Detector Reset" at the control panel.
Dip-
switch
5 on ON =
This line is released by a line connected in series.
Important:
switched OFF/ON for "Smoke Detector Reset" at the control panel.
Connection RT 45 on LE 513 and connection GE 628 (-L) V2
external
control
operating
contact
10kW
penultimate
1
1
2
< optional >
X5
RM
VE
6/16
RZN 43xx-E
-
line plug-in card for connecting of
maximum 14 fire detectors and 8
smoke vent buttons each
-
Functions:
-
line On/ Off
-
alarm/ fault
DIP-switch
factory setting
Every previous plug-in slot for the triggering line and group must be occupied. Both the lines must be
Every previous plug-in slot after the releasing line must be occupied! Both the lines must be
fire
detector
smoke vent button
type***
RT 45
W
10k *
out
last
in
2
8
3
1
10kW
out
8
first to
2
3
1
in
W
10k *
1
2
3
4
5
RM
RT
LE
O N
1
2
3
4
5
Vent button
LT 43
(-SD)
L
P
6
4
7
5
6
4
7
5
L
P
1
2
3
6
7
8
LT
* For detailed information concerning the connection,
please refer to the instruction for use of respective drive.
Detector Cables (Line):
The detector cables are monitored for short
circuit and break.
The opening device is automatically triggered
and opens up in the case of a fault, if DIP-switch
1+2 are set to ON.
Smoke vent button cable and cable from
automatic detectors:
- Weak current sheathed flexible cable YR 6 x
0.8
or
- Domestic wiring cable IY(ST)Y 4 x 2 x 0.6
drives*
terminal module
EM 47 K
Mot. a
Mot. b
-HS*
branch
box by customer
Mot. a
Mot. b
-HS*
lenght of line and cross
sections, see page 9
4
5
6
7
MOT
GE
last
drive
first to
penultimate
drive
99.821.70 3.5/01/12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzn 4308-eRzn 4316-eRzn 4332-eRzn 4364-e

Table of Contents