Connection of fire detector
Max. 14 fire detectors connectable.
Only D+H approved detectors must be used.
Terminal resistor*
10kW
1
2
RM
RZN 4503-T

Line shutdown

If the LED line fault flashes, the line is switched off,
e.g. for service reasons. You cannot activate the
control panel in this status.
In case of an actual line error the LED line fault is
permanently on.
Triggerng an alarm is not possible during the
shutdown.
Display
Display
Display
"line fault"
"system
"general
OK"
fault"
= Display ON
99.825.18 2.1/10/13
< optional >
FO 1362
or
FT 1262
7
FO 1362
or
FT 1262
7
RT
Description
Line fault
Line deactivated
Servicetimer is up
= Display flashing
= Display OFF
Connection of fire alarm system
B
E
* Terminal resistors for line monitoring
It is pinched in control panel for transport.
Take it off there and connect according to plan.
Terminal resistor must remain at terminal RM 1,2,
when no fire detector or external control exists!
** Remove the 180R resistor

Drives

Group output:
Three minutes after the motor group has been
operated in OPEN or CLOSE direction, the
potential between Mot.a and Mot.b is switched to
zero potential. While an alert, a possible group
disturbance will not notified. Only after reset the
alarm, a fault message will be indicated.
High-speed function (HS):
All D+H drives with SHEV high-speed function are
supported. In daily ventilation operation, a consi-
derable noise reduction is achieved through the
reduced drive speed. In case of SHEV the drives
run with a very high speed to reach the OPEN
position defined within 60 seconds at the most.
SHEV retriggering:
The smoke vents will be triggered with an OPEN-
impulse every 2 minutes for a duration of 30
minutes according to VdS 2581. For this, the
drives must be blockage safe. All D+H drives meet
this precondition. Otherwise the DIP switches has
to be switched on OFF.
Mounting of the drives:
Please take mounting informations from the
relevant instruction for use of the respective drive,
because of varied possibilities for choosing drives.
English
BMZ / BMA
Operating contact
Alarm resistor
1kW
Terminal resistor*
10kW
R
RM
RT
RZN 4503-T
RZN 4503-T
29/36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents