Smoke vent control panel
Hide thumbs Also See for RZN 43-E Series:
Table of Contents

Advertisement

Line plug-in card LE 513 (continuation)
Parallel connection of RT 45 on LE 513
shunt connection
by customer
*
Terminal resistor for line monitoring:
They are secured in the control panel for transport.
Take them out and connect them in accordance with the plan.
The
Terminal resistor
must remain in terminal clamp L 1,2 if no fire
detector or external control is present.
**
Maximum total cut-off current
of connected drives:
RZN 4308-E
=
8A
RZN 4316-E
=
16A
RZN 4332-E
=
32A
RZN 4364-E
=
64A
No more than 10A on one group plug-in card.
*** Fire detectors
Only D+H - approved detectors permissible.
**** Thermal fire recognition element,
optional, is required by some fire authorities.
99.821.70 3.5/01/12
Smoke vent button
1st line
RT 45
last smoke
vent button
each
2
8
3
1
first to
8
penultimate
smoke vent
2
3
1
button each
10kW
1
3
4
5
2
RM
LE
Smoke vent button
6
4
7
5
2
6
4
7
5
6
7
8
1
RT
X5
VE
2nd line
RT 45
8
3
1
6
4
7
5
10kW
8
2
3
1
6
4
7
5
RZN 43xx-E
7/16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzn 4308-eRzn 4316-eRzn 4332-eRzn 4364-e