Clean The Condensate Drain; Gas-Side Maintenance; Clean The Burner - State Water Heaters SCC 40-40 Installation, User And Service Manual

Table of Contents

Advertisement

11.3.2
11.4
11.4.1
0312884_SCC_UKUK_V1.0, 2017-10-03

Clean the condensate drain

To clean the condensate drain:
1.
Place a tray or towels under the condensate drain to collect water leakage.
2.
Remove the condense trap (2) at the bottom of the condensate drain (1).
3.
Empty the condense trap and clean it with water.
4.
Make sure that there is no grit or other blockages in the condense trap.
5.
Make sure that there is no grit or other blockages in the condensate drain.
6.
Make sure that there is no grit or other blockages in the drain pipe (3).
7.
Make sure that the slope of the drain pipe is correct; 5 mm/m.
8.
Install the condense trap onto the condensate drain.
Fig. Condensate drain
3

Gas-side maintenance

Do gas side maintenance when the water heater does not operate correctly, the air
pressure differential is not correct and/or the CO
To do gas side maintenance:
Clean the burner (see section 11.4.1)
Clean the combustion chamber (see section 11.4.2)

Clean the burner

Remove the burner engine:
1.
Close the gas control valve, refer to Installation diagram (see section 8.3).
2.
Disconnect all plugs from the burner engine (1).
3.
Disconnect the gas supply pipe (2).
4.
Loosen the two bolts (3) to disconnect the burner engine (4) from the adapter.
5.
Take the burner engine out of the water heater.
2
1
value is not correct.
2
1. Condensate drain
2. Condense trap
3. Drain pipe
65

Advertisement

Table of Contents
loading

Table of Contents