Piping installation

17.1.8 Piping length: VRV DX and RA DX

Installer and user reference guide
80
Maximum allowable length after branch
The pipe length from the first refrigerant branch kit to the indoor unit ≤40 m.
Example 1: unit 8: b+c+d+e+f+g+p≤40 m
Example 2: unit 6: b+h≤40 m, unit 8: i+k≤40 m
Example 3: unit 8: i≤40 m, unit 2: c≤40 m
For system containing VRV DX indoor units and RA DX indoor units:
System setup
a
H4
H5
H1
Header
BP box
1~5 RA DX indoor units
6,7 VRV DX indoor units
Maximum allowable length
Between outdoor unit and indoor unit.
Actual piping length
(a)
Equivalent length
Total piping length
(a)
Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes of equivalent piping length, not for refrigerant charge calculations).
Between BP unit and indoor unit.
Indoor unit capacity index
<60
60
71
Remark: Minimum allowable length between outdoor unit and first refrigerant
branch kit>5 m (the refrigerant noise from the outdoor unit can be transmitted).
Example: a>5 m
b
A
B
c
e
f
BP1
6
k
1
2
3
H2
4
100 m
Example:
a+b+g+l≤100 m
120 m
250 m
Example:
a+b+d+g+l+k+c+e+f+h+i+j≤250 m
d
g
7
BP2
H6
l
5
Pipe length
2~15 m
2~12 m
2~8 m
4P546228-1C – 2021.11